| Plan Review Notes For Permit 20081194 |
| Permit Number |
20081194 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2020-09-11 11:24:19 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | FLORIDA BUILDING CODE 2017 6TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | | NFPA 70 2014 EDITION | | | | | | JAKE LEAHY BN, BU, PX | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | 1) PLANS ARE NOT REAL CLEAR AS TO HOW MANY DIFFERENT | | | FIXTURES ARE INVOLVED PLEASE CLEARIFY | | | | | | 2) PLEASE INDICATE ON CUT SHEETS FIXTURE BEING USED NOT | | | INDUCATED ON CUT SHEETS | | | | | | 3) VALUE OF WORK SHOWN ON PLANS IS LOW PLEASE INCLUDE A | | | SIGNED CONTRACT FOR THE SITE LIGHTING. |
|