| 2020-09-17 12:01:55 | PLAN REVIEW GENERATOR / BUILDING | | | | | | CHRISTOPHER S. THROOP, C.B.O. | | | PLANS EXAMINER BUILDING - PX3169 | | | PLANS EXAMINER 1&2 FAMILY - SFP306 | | | CONSTRUCTION SERVICES DIVISION | | | TEL: 561-805-6726 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | CODES IN EFFECT: | | | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | | | | 2ND REVIEW | | | | | | RESULTS: DENIED | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | COMMENTS FROM 1ST REVIEW HAVE NOT BEEN ADDRESSED. SEE | | | BELOW. | | | | | | 1. THE GENERATOR SPECIFICATIONS PROVIDED ARE | | | INCOMPLETE. THE GENERATOR SIZE AND WEIGHT ARE REQUIRED | | | TO VERIFY COMPLIANCE WITH THE GENERATOR PAD | | | REQUIREMENTS. | | | THE GENERATOR PAD SCHEDULE SPECIFIES THE MINIMUM | | | GENERATOR SIZE, WEIGHT AND DSIGN WIND LOADS REQUIRED. | | | SEE NOTE AT THE BOTTOM OF PAGE 5 OF THE GENERATOR | | | SPECIFICATIONS PROVIDED. | | | | | | | | | 2. PROVIDE SITE SPECIFIC DESIGN WIND LOADS FOR THE | | | GENERATOR PER NOTE #2 OF ALLOWABLE DESIGN PRESSURE | | | REQUIREMENT OF THE GENERATOR PAD. | | | | | | 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS | | | SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH | | | 107.2.5. | | | |
|