Plan Review Notes
Plan Review Notes For Permit 20081133
Permit Number 20081133
Review Stop B
Sequence Number 1
Notes
Date Text
2020-09-15 09:31:17PLAN REVIEW GENERATOR / BUILDING
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. THE GENERATOR SPECIFICATIONS PROVIDED ARE
 INCOMPLETE. THE GENERATOR SIZE AND WEIGHT ARE REQUIRED
 TO VERIFY COMPLIANCE WITH THE GENERATOR PAD
 REQUIREMENTS.
 THE GENERATOR PAD SCHEDULE SPECIFIES THE MINIMUM
 GENERATOR SIZE, WEIGHT AND DSIGN WIND LOADS REQUIRED.
 SEE NOTE AT THE BOTTOM OF PAGE 5 OF THE GENERATOR
 SPECIFICATIONS PROVIDED.
  
  
 2. PROVIDE SITE SPECIFIC DESIGN WIND LOADS FOR THE
 GENERATOR PER NOTE #2 OF ALLOWABLE DESIGN PRESSURE
 REQUIREMENT OF THE GENERATOR PAD.
  
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
  
2020-08-29 10:10:09ELECTRICAL LOAD CALCS AND RISER REQUIRE CONTRACTORS
 SIGNATURE. CT