2020-09-21 14:22:33PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE SCOPE OF WORK IS NOT CLEAR FOR THIS PROJECT. THE
 PERMIT APPLICATION STATES THAT THE SCOPE OF WORK IS TO
 ADD ONE NEW BATHROOM. THE SCOPE OF WORK ON THE PLAN IS
 TO REMODEL TWO EXISTING BATHROOMS. PLEASE CLARIFY. FBC
 107.2.1
  
 2) SUBMIT AN EXISTING FLOOR PLAN AND A PROPOSED FLOOR
 PLAN THAT SHOW THE ENTIRE HOUSE AND THE LOCATION OF ALL
 ROOMS. FBC 107.2.1
  
 3) SUBMIT A SIGNED COPY OF THE CONTRACT FOR THE WORK
 UNDER THIS PERMIT WITH SCOPE OF WORK AND COSTS. FBC
 109.3 BUILDING PERMIT VALUATION.
  
 4) FBC 107.2.1 - INFORMATION ON CONSTRUCTION DOCUMENTS.
 ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF
 THE PERSON RESPONSIBLE FOR THE DESIGN.
  
  