| Date |
Text |
| 2020-09-17 09:35:55 | 1ST REVIEW FBC-2017 RES. |
| | PERMIT- 20081107 |
| | 9/17/2020 |
| | |
| | CODES IN EFFECT: |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| | EDITION 2017 |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) THE $18,500 TOTAL VALUE ON THE APPLICATION AND ON |
| | THE CONTRACT DOES NOT APPEAR TO INCLUDE THE $4500.00 |
| | COST OF THE GAS PIPING INSTALLATION AS SHOWN ON THE |
| | SUB-PERMIT APPLICATION. THE TOTAL VALUE MAY HAVE TO |
| | INCREASE TO $23,000.00- SECTION 109.3 WPB. |
| | |
| | 2) THE LP TANK TIE DOWN DETAIL DESIGNED BY ATCHLEY P.E |
| | HAS AN OUTDATED STANDARD SEAL AND SIGNATURE, AND ALSO |
| | APPEARS TO BEAR A COPIED ELECTRONIC SEAL. THIS DOCUMENT |
| | AND DETAILS SHALL BEAR AN ORIGINAL ELECTRONIC SEAL AND |
| | SIGNATURE TO BE VALID FOR PERMITTING- FL. STATUTES |
| | 471.02=03, 471.025, AND FAC 61G15-23.005. IN LIEU OF |
| | UPLOADING A VERIFIABLE ELECTRONICALLY SIGNED AND SEALED |
| | DETAIL, AN ORIGINAL PAPER COPY MAY BE PHYSICALLY |
| | DELIVERED TO THE WPB BUILDING DEPARTMENT. PLEASE |
| | CONTACT ME IF YOU HAVE QUESTIONS ABOUT THE SUBMITTAL. |
| | |
| | 3) CATHODIC PROTECTION SYSTEM- SECTIONS 5.2.1.11 & |
| | 6.6.6.1(I) NFPA 58. SHOW ON THE RISER DRAWING THE TYPE |
| | OF CATHODIC PROTECTION TO BE PROVIDED. IF USING A |
| | CLOTH-BAGGED ANODE, INDICATE THE SIZE OF THE ANODE AND |
| | SHOW WHERE IT WILL BE LOCATED. SPECS FOR THE ANODE CAN |
| | BE SUBMITTED WITH CORRECTED PLANS OR BE ONSITE FOR |
| | INSPECTION. |
| | |
| | 3) GAS RISER: |
| | A) ACCORDING TO THE SUBMITTED SPECS THE GENERATOR HAS A |
| | 340,000 BTUH LOAD- (136 X 2500= 340,000) AND A 7-11 |
| | IN.WC. INPUT PRESSURE RATING. PLEASE CORRECT THE RISER. |
| | |
| | B) INDICATE THE PE AND SCHEDULE 40 METALLIC PIPE SIZING |
| | TABLES ON THE DRAWING- SEE TABLES G2413.4(1)- |
| | G2413.4(8) FBC RES. SHOW THE THE SIZE OF THE METALLIC |
| | PIPE. |
| | |
| | C) INDICATE THE MAKE AND MODEL OF THE REGULATOR ON THE |
| | DRAWING AND SUBMIT MANUFACTURER'S SPECIFICATIONS MARKED |
| | UP TO SHOW THE INLET AND OUTLET SIZES AND PRESSURES, |
| | AND ORIFICE SIZES- SECTION G2421.1 & G2421.2 FBC RES. |
| | SHOW THE LOCATIONS OF THE REQUIRED PIPE UNIONS WITHIN 1 |
| | FT. ON EACH SIDE OF THE REGULATORS- SECTION G2421.2 |
| | (7). |
| | |
| | D) SUBMIT MANUFACTURER'S SPECS FOR THE GENERATOR FLEX |
| | CONNECTOR THAT INDICATE MANUFACTURER AND MODEL, LISTING |
| | STANDARDS, AND INSTALLATION GUIDELINES- SECTION |
| | G2415.1. |
| | |
| | E) INDICATE THE BURIAL DEPTH OF THE PE PIPING- SECTION |
| | G2415.12 AND SHOW A TRACER WIRE WILL BE INSTALLED |
| | ADJACENT TO THE PIPE- SECTION G2415.17.3. |
| | |
| | F) SHOW HOW THE PE PIPING RISER WILL CONNECT TO THE |
| | METALLIC PIPE PER SECTIONS G2415.17.1 & G2415.17.2. |
| | PLEASE NOTE THAT SPECS FOR ANODELESS RISERS AND |
| | PE/METALLIC PIPE CONNECTORS SHALL BE LISTED AND |
| | LABELED. |
| | |
| | 4) SURVEY: THE GENERATOR SHALL BE INSTALLED A MINIMUM |
| | OF 5 FT. FROM COMBUSTIBLE WALLS. THE 18 IN. CLEARANCE |
| | DISTANCE SHALL BE PERMITTED IF THE HOUSE WALL HAS A |
| | 1-HR. FIRE RESISTANCE RATING, OR THE GENERATOR HAS A |
| | WEATHERPROOF ENCLOSURE CONSTRUCTED OF NON-COMBUSTIBLE |
| | MATERIALS AND IT HAS BEEN DEMONSTRATED THAT A FIRE |
| | WITHIN THE ENCLOSURE WILL NOT IGNITE COMBUSTIBLE |
| | MATERIALS OUTSIDE OF THE ENCLOSURE- SECTION 4.1.4 NFPA |
| | 37. PLEASE SUBMIT THE GENERATOR INSTALLATION GUIDELINES |
| | FROM THE MANUFACTURER. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL/PLUMBING PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | [email protected] |
| | |