Plan Review Notes
Plan Review Notes For Permit 20081106
Permit Number 20081106
Review Stop P
Sequence Number 1
Notes
Date Text
2020-09-04 09:18:1009/04/20 2ND PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 AS NOTED ON THE MASTER, AREAS THAT ARE SPECIFIED TO
 HAVE NO PERMIT OR INSPECTIONS WILL HAVE A FULL
 EVALUATION DONE IN FIELD AND PLAN WILL REQUIRE
 INFORMATION AS FOLLOW;
  
 1. PLEASE PROVIDE A SANITARY ( INCLUDE GREASE
 INTERCEPTOR, VENTS, FLOOR SINKS, CLEAN-OUTS, ETC.) AND
 WATER ( SHUTOFF VALVES, AIR ARRESTORS, TRAP PRIMER,
 ETC) ISOMETRIC DIAGRAMS PER THE WPB AMENDMENTS TO THE
 FBC SEC. 107.5.1.3 (13) COMMERCIAL PLUMBING.
  
 2. PLEASE PROVIDE A DETAIL OF THE THREE COMPARTMENT
 SINK PER THE 2017 FBC P 802.1.1 FOOD HANDLING.
  
 3. THE WATER HEATER IN THE MEZZANINE, PLEASE PROVIDE A
 DETAIL DRAWING AND SHOW WHERE THE DRAIN PAN IS DRAIN
 OUT TO, EXPANSION DEVICE, SHUTOFF, ETC. PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 4. PROVIDE A NOTE FOR THE ICEMAKER, IT SHALL BE
 EQUIPPED WITH AN IN-LINE VACUUM BREAKER THAT COMPLIES
 WITH ASSE 1024 PER THE 2017 FBC SEC. 608.13.10.
  
 5. JANITORS SINK (MOP SINK) SURROUNDING WALL SHALL BE
 IN ACCORDANCE WITH A NON-ABSORBENT SURFACE IN
 ACCORDANCE WITH THE 2017 FBC BUILDING SEC. 1210.2.2.
 PLEASE MAKE A NOTE ON THIS SHEET OR SHOW A DETAIL.
  
 6. SUBMIT A SLAB REPAIR DETAIL AND SHOW THE WIDTH OF
 THE REPAIR, THE MINIMUM THICKNESS OF THE CONCRETE TO BE
 REPLACED, AND THE PSI OF THE CONCRETE. SHOW THE SIZE
 AND LENGTH OF THE DOWELS, THE MINIMUM EMBEDMENT DEPTH
 INTO THE EXISTING SLAB, THE ANCHORING MATERIAL FOR THE
 DOWELS AND THE SPACING OF THE DOWELS ON CENTER. THE
 REPAIR SHALL ALSO INCLUDE TERMITE TREATMENT OF THE SOIL
 AND THE REQUIRED VAPOR BARRIER OVER WELL-COMPACTED
 SOIL. A COPY OF THE TERMITE CERTIFICATE SHALL BE ONSITE
 FOR A FINAL INSPECTION.
  
 7. ALL RESTROOMS WITH ACCESSIBILITY REQUIRE DETAIL FOR
 GRAB BARS PLACEMENT, CLEAR FLOOR SPACE DIMENSION,
 MIRROR HEIGHT, LAV HEIGHTS, ETC. PER THE WPB FBC
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 8. THERE ARE TWO HAND SINK IN THE FOOD PREP, ARE THEY
 FOR HAND WASHING OR FOOD PREP SINCE THERE ARE IN THE
 FOOD PREP AREA AND WILL THEY BE INDIRECTLY WASTED PER
 THE 2017 FBC SEC. P 1003.1
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR