Plan Review Notes
Plan Review Notes For Permit 20081095
Permit Number 20081095
Review Stop E
Sequence Number 2
Notes
Date Text
2020-10-28 13:25:59FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 ENRIQUE QUINONEZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6746
 [email protected]
  
 1ST REVIEW:
  
 1. SMOKE DETECTORS MISSING INSIDE BEDROOM #2, OUTSIDE
 BEDROOM #2, OUTSIDE BEDROOM #3 AND OUTSIDE MASTER
 BEDROOM PER R314.3.
 R314.3 LOCATION.
 SMOKE ALARMS SHALL BE INSTALLED IN THE FOLLOWING
 LOCATIONS:
 1.IN EACH SLEEPING ROOM.
 2.OUTSIDE EACH SEPARATE SLEEPING AREA IN THE IMMEDIATE
 VICINITY OF THE BEDROOMS.
  
 2. PROVIDE LUMINAIRE AND OUTLET FOR MECHANICAL
 EQUIPMENT IN ATTIC PER M1305.1.3.1.
 PROVIDE GFCI PROTECTED OUTLET AND SWITCH CONTROLLED
 LIGHT FOR SERVICING EACH AHU LOCATED IN AN ATTIC. FBC
 MECHANICAL CODE M306.3.1
  
 2ND REVIEW:
  
 1. SMOKE DETECTORS MISSING INSIDE BEDROOM #2, OUTSIDE
 BEDROOM #2, OUTSIDE BEDROOM #3 AND OUTSIDE MASTER
 BEDROOM PER R314.3.
 R314.3 LOCATION.
 SMOKE ALARMS SHALL BE INSTALLED IN THE FOLLOWING
 LOCATIONS:
 1.IN EACH SLEEPING ROOM.
 2.OUTSIDE EACH SEPARATE SLEEPING AREA IN THE IMMEDIATE
 VICINITY OF THE BEDROOMS.
  
 COMPLETED.
  
 2. PROVIDE LUMINAIRE AND OUTLET FOR MECHANICAL
 EQUIPMENT IN ATTIC PER M1305.1.3.1.
 PROVIDE GFCI PROTECTED OUTLET AND SWITCH CONTROLLED
 LIGHT FOR SERVICING EACH AHU LOCATED IN AN ATTIC. FBC
 MECHANICAL CODE M306.3.1
  
 COMPLETED
  