| 2020-09-08 10:29:21 | PLAN REVIEW / ELECTRICAL | | | | | | CHRISTOPHER S. THROOP, C.B.O. | | | PLANS EXAMINER BUILDING - PX3169 | | | PLANS EXAMINER 1&2 FAMILY - SFP306 | | | CONSTRUCTION SERVICES DIVISION | | | TEL: 561-805-6726 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | CODES IN EFFECT: | | | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | NEC 2014 | | | | | | 1ST REVIEW | | | | | | RESULTS: DENIED | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | 1. SMOKE DETECTORS MISSING INSIDE BEDROOM #2, OUTSIDE | | | BEDROOM #2, OUTSIDE BEDROOM #3 AND OUTSIDE MASTER | | | BEDROOM PER R314.3. | | | R314.3 LOCATION. | | | SMOKE ALARMS SHALL BE INSTALLED IN THE FOLLOWING | | | LOCATIONS: | | | 1.IN EACH SLEEPING ROOM. | | | 2.OUTSIDE EACH SEPARATE SLEEPING AREA IN THE IMMEDIATE | | | VICINITY OF THE BEDROOMS. | | | | | | 2. PROVIDE LUMINAIRE AND OUTLET FOR MECHANICAL | | | EQUIPMENT IN ATTIC PER M1305.1.3.1. | | | PROVIDE GFCI PROTECTED OUTLET AND SWITCH CONTROLLED | | | LIGHT FOR SERVICING EACH AHU LOCATED IN AN ATTIC. FBC | | | MECHANICAL CODE M306.3.1 | | | | | | | | | | | | | | | | | | | | | | | | |
|