2020-09-17 12:38:27THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 THE FOLLOWING COMMENTS ARE PROVIDED IN AN EFFORT TO
 REDUCE FALSE/NUISANCE ALARMS AND NON-REQUIRED DEVICES:
  
  
 1) THERE ARE TWO SD IN THE STORAGE ROOM.
  
 9.6.2.9 WHERE A TOTAL (COMPLETE) COVERAGE SMOKE
 DETECTION
 SYSTEM IS REQUIRED BY ANOTHER SECTION OF THIS CODE,
 AUTOMATIC
 DETECTION OF SMOKE IN ACCORDANCE WITH NFPA 72, NATIONAL
 FIRE
 ALARM AND SIGNALING CODE, SHALL BE PROVIDED IN ALL
 OCCUPIABLE
 AREAS IN ENVIRONMENTS THAT ARE SUITABLE FOR PROPER
 SMOKE DETECTOR
 OPERATION.
  
 COMPLETE SD COVERAGE IS NOT REQUIRED.
  
 PLEASE ELIMINATE THE ONE IN THE CENTER.
  
  
 2) THERE IS A SD IN THE CUST. CLOSET.
  
 I DON'T BELIEVE ONE IS REQUIRED IN THIS ROOM AS LONG AS
 THERE IS A FIRE SPRINKLER LOCATED IN THE ROOOM AND THE
 SD WOULD NOT BE REQUIRED.
  
 AS THIS APPAERS TO BE A SMALL ASSEMBLY OCCUPANCY WITH
 INCIDENTAL OTHER OCCUPANCIES, A SD IS NOT REQUIRED
  
 9.6.2.9 WHERE A TOTAL (COMPLETE) COVERAGE SMOKE
 DETECTION
 SYSTEM IS REQUIRED BY ANOTHER SECTION OF THIS CODE,
 AUTOMATIC
 DETECTION OF SMOKE IN ACCORDANCE WITH NFPA 72, NATIONAL
 FIRE
 ALARM AND SIGNALING CODE, SHALL BE PROVIDED IN ALL
 OCCUPIABLE
 AREAS IN ENVIRONMENTS THAT ARE SUITABLE FOR PROPER
 SMOKE DETECTOR
 OPERATION.
  
 12.3.4.2.3* IN ASSEMBLY OCCUPANCIES WITH OCCUPANT LOADS
 OF MORE
 THAN 300, AUTOMATIC DETECTION SHALL BE PROVIDED IN ALL
 HAZARDOUS
 AREAS THAT ARE NOT NORMALLY OCCUPIED, UNLESS SUCH AREAS
 ARE
 PROTECTED THROUGHOUT BY AN APPROVED, SUPERVISED
 AUTOMATIC
 SPRINKLER SYSTEM IN ACCORDANCE WITH SECTION 9.7.
  
 COMPLETE SD COVERAGE IS NOT REQUIRED.
  
 PLEASE REVIEW AND CORRECT.
  
  
  
 3) THERE ARE INDICATIONS OF 3 PULL STATIONS AT 3 EXIT
 DOORS.
  
 I UNDERSTAND THE CODE THAT SAYS THERE SHALL BE PS AT
 EACH EXIT; HOWEVER, THERE IS A PROVISION FOR REDUCTION
 OF PS.
  
 PER NFPA 101 CH 9
  
 9.6.2.6* FOR FIRE ALARM SYSTEMS USING AUTOMATIC FIRE
 DETECTION OR
 WATERFLOW DETECTION DEVICES TO INITIATE THE FIRE ALARM
 SYSTEM IN
 ACCORDANCE WITH CHAPTERS 11 THROUGH 43, NOT LESS THAN
 ONE MANUAL
 FIRE ALARM BOX, LOCATED AS REQUIRED BY THE AUTHORITY
 HAVING
 JURISDICTION, SHALL BE PROVIDED TO INITIATE A FIRE
 ALARM SIGNAL.
  
 PLEASE ELIMINATE THE 2 PULL STATIONS IN THE WORK-OUT
 AREA.
  
 PLEASE REVIEW AND CORRECT.
  
  
 4) THERE IS A INDICATION OF A HORN STROBE IN THE
 STORAGE ROOM.
  
 AS THIS ROOM IS SMALL AND NOT NORMALLY OCCUPIABLE AND
 TWO HORN STROBES ARE LOCATED IN THE ROOM DIRECTLY
 ADJACENT TO THE STORAGE ROOM A HORN STROBE IS NOT
 REQUIRED.
  
 PLEASE REVIEW AND CORRECT.
  
  
  
 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  