| 2020-09-25 16:10:23 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC SIXTH EDITION (2017) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) IN A COUPLE OF PLACES ON SHEET S-1, THE ENGINEER | | | SPECIFIES THAT THE DESIGN IS BASED ON ASCE 7 -16. | | | CHAPTER 35 OF THE 2017 FBC REFERENCES ASCE 7-10. THE | | | BUILDING CODE HAS NOT YET ADOPTED ASCE 7-16. PLEASE | | | REVISE. | | | | | | |
|