2020-09-24 13:38:45CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 20081056 516 24TH ST
  
  
 1ST REVIEW
 PLUMBING COMMENTS: DENIED
 A REVIEW OF MINIMUM PLUMBING FIXTURE REQUIREMENTS AS
 REQUIRED BY FBC ACC IS PART OF THE PLUMBING REVIEW
 PROCESS BUT IS TYPICALLY ADDRESSED ON THE ARCHITECTURAL
 PLANS. ANY COMMENTS CONCERNING THESE REQUIREMENTS MUST
 BE SATISFACTORILY ADDRESSED PRIOR TO A PLUMBING REVIEW
 APPROVAL.
  
 LS1-0 LIFE SAFETY PLAN OCCUPANCY TYPE B;
 BUSINESS OCCUPANCY LOAD; 19
  
 1.PER FBC PL TABLE 403.1, PROVIDE ONE (1) SERVICE SINK
  
 2.PER FBC PL TABLE 403.1, A DRINKING FOUNTAIN IS
 REQUIRED. PER FBC PL SECTION 410.3 AND FBC ACC 211.2,
 PROVIDE HIGH AND LOW DRINKING FOUNTAINS.
 WHERE DRINKING FOUNTAINS ARE REQUIRED, NOT FEWER THAN
 TWO DRINKING FOUNTAINS SHALL BE PROVIDED. ONE DRINKING
 FOUNTAIN SHALL COMPLY WITH THE REQUIREMENTS FOR PEOPLE
 WHO USE A WHEELCHAIR AND ONE DRINKING FOUNTAIN SHALL
 COMPLY WITH THE REQUIREMENTS FOR STANDING PERSONS.
 EXCEPTIONS:
 A SINGLE DRINKING FOUNTAIN WITH TWO SEPARATE SPOUTS
 THAT COMPLIES WITH THE REQUIREMENTS FOR PEOPLE WHO USE
 A WHEELCHAIR AND STANDING PERSONS SHALL BE PERMITTED TO
 BE SUBSTITUTED FOR TWO SEPARATE DRINKING FOUNTAINS.
  
 3.RE: PLAN SHEET A.1
 A.PER WPB FBC 107.2.1, PROVIDE FULL BATHROOM DETAIL OF
 FLOOR PLAN, FRONT, REAR AND SIDE WALL ELEVATIONS AS
 REQUIRED TO PROVIDE COMPREHENSIVE INFORMATION FOR
 ACCESSIBILITY COMPLIANCE. SEE COMMENTS BELOW CONCERNING
 EXISTING DETAILS AS WELL AS OTHER REQUIREMENTS.
 B.WATER CLOSET GRAB BARS FRONT ELEVATION DOES NOT MATCH
 THE CLEAR FLOOR SPACE AT TOILET DETAIL AND DOES NOT
 COMPLY WITH THE FOLLOWING:
 C.FBC ACC 604.2; THE WATER CLOSET SHALL BE POSITIONED
 WITH A WALL OR PARTITION TO THE REAR AND TO ONE SIDE.
 THE CENTERLINE OF THE WATER CLOSET SHALL BE 16 INCHES
 MINIMUM TO 18 INCHES MAXIMUM FROM THE SIDE WALL OR
 PARTITION
 D.FBC ACC 604.5.2; THE REAR WALL GRAB BAR SHALL BE 36
 INCHES LONG MINIMUM AND EXTEND FROM THE CENTERLINE OF
 THE WATER CLOSET 12 INCHES MINIMUM ON ONE SIDE AND 24
 INCHES MINIMUM ON THE OTHER SIDE. FBC ACC 604.5.2
 E.FBC ACC 604.6; FLUSH CONTROLS SHALL BE HAND OPERATED
 OR AUTOMATIC. HAND OPERATED FLUSH CONTROLS SHALL COMPLY
 WITH 309. FLUSH CONTROLS SHALL BE LOCATED ON THE OPEN
 SIDE OF THE WATER CLOSE.
 F.RE: WATER CLOSET GRAB BARS FRONT ELEVATION; TOILET
 PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND SHALL BE 7
 INCHES MINIMUM AND 9 INCHES MAXIMUM IN FRONT OF THE
 WATER CLOSET MEASURED TO THE CENTERLINE OF THE
 DISPENSER. THE OUTLET OF THE DISPENSER SHALL BE 15
 INCHES MINIMUM AND 48 INCHES MAXIMUM ABOVE THE FINISH
 FLOOR AND SHALL NOT BE LOCATED BEHIND GRAB BARS PER FBC
 ACC 604.8.
 J.MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS SHALL
 BE INSTALLED WITH THE BOTTOM EDGE OF THE REFLECTING
 SURFACE 40 INCHES MAXIMUM ABOVE THE FINISH FLOOR OR
 GROUND. MIRRORS NOT LOCATED ABOVE LAVATORIES OR
 COUNTERTOPS SHALL BE INSTALLED WITH THE BOTTOM EDGE OF
 THE REFLECTING SURFACE 35 INCHES MAXIMUM ABOVE THE
 FINISH FLOOR OR GROUND PER FBC ACC 603.3.
  
 4.PER WPB FBC 107.2.1, SHOW LOCATION OF REQUIRED
 DRINKING FOUNTAIN(S); PROVIDE ACCESSIBILITY DETAILS
 INCLUDING PLAN AND ELEVATION DETAILS SHOWING COMPLIANCE
 WITH FBC ACC CHAPTERS 2, 3 AND 6.
  
 5.PER WPB FBC 107.2.1, PROVIDE ACCESSIBILITY DETAILS
 FOR BREAKROOM SINK (REQUIRED FOR COMPLIANCE WITH FBC
 ACC 212.3) INCLUDING PLAN AND ELEVATION DETAILS SHOWING
 COMPLIANCE WITH FBC ACC CHAPTERS 3 AND 6. SINKS SHALL
 BE INSTALLED WITH THE FRONT OF THE HIGHER OF THE RIM OR
 COUNTER SURFACE 34 INCHES MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND PER FBC ACC 606.3.
  
 6.PER WPB FBC 107.2.1, INDICATE ON ARCHITECTURAL FLOOR
 PLAN ALL REQUIRED CLEAR FLOOR SPACES FOR ACCESSIBLE
 PLUMBING FIXTURES.
  
 7.RE: D1-0 DEMOLITION PLAN; ACCORDING TO P1.1, THERE IS
 APPARENTLY AN EXISTING PLUMBING INFRASTRUCTURE. PER WPB
 FBC 107.1, SHOW EXISTING PLUMBING FIXTURES THAT ARE TO
 BE REMOVED AND PROVIDE DIRECTION FOR DECOMMISSIONING OF
 EXISTING FIXTURES AND SAFEING/CAPPING OF PLUMBING
 OPENINGS/CONNECTIONS.
  
 8.PER WPB FBC 107.2.1, PROVIDE BACK MANUFACTURER'S
 SPECIFICATION/INSTALLATION MANUAL FOR THE ICE MAKER.
 (SEE P1.1 DOMESTIC WATER KEYNOTE #2)
  
 9. RE: P2.1:
  
 A.DETAIL 5, ELECTRIC WATER HEATER PIPING DIAGRAM;
 A1.PER FBC PL 504.2, BOTTOM FED WATER HEATERS AND
 BOTTOM FED TANKS CONNECTED TO WATER HEATERS SHALL HAVE
 A VACUUM RELIEF VALVE INSTALLED. THE VACUUM RELIEF
 VALVE SHALL COMPLY WITH ANSI Z21.22.
 A2.PER FBC PL 504.6 (5), T & P RELIEF VALVE SHALL
 DISCHARGE TO THE FLOOR, TO THE PAN SERVING THE WATER
 HEATER OR STORAGE TANK, TO A WASTE RECEPTOR OR TO THE
 OUTDOORS. DETAIL INDICATES DISCHARGE TO OPEN DRAIN. PER
 WPB FBC 107.2.1, PROVIDE OPEN DRAIN ON SANITARY PIPING
 FLOOR PLAN AND RISER DIAGRAM OR DISCHARGE TO PAN WITH
 APPROPRIATE AIR GAP OR TO THE OUTDOORS. BE SPECIFIC.
 A3.COMPLY WITH FBC PL 607.3. PER WPB FBC 107.2.1,
 SPECIFY, LOCATE AND SIZE A THERMAL EXPANSION CONTROL
 DEVICE IN THE COLD WATER SUPPLY PIPE AT A POINT THAT IS
 DOWNSTREAM OF ALL CHECK VALVES, PRESSURE REDUCING
 VALVES AND BACKFLOW PREVENTERS. THERMAL EXPANSION
 CONTROL DEVICES SHALL BE SIZED IN ACCORDANCE WITH THE
 MANUFACTURER?S INSTRUCTIONS AND SHALL BE SIZED SUCH
 THAT THE PRESSURE IN THE WATER DISTRIBUTION SYSTEM
 SHALL NOT EXCEED THAT REQUIRED BY SECTION 604.8.
 A4.DETAIL INDICATES 140 DEGREE WATER FROM WATER HEATER
 TO A LEONARD TM-520-LF-QT THERMOSTATIC MIXING VALVE
 WHICH IS CAPABLE OF DELIVERING 1 ? 72 GPM. THE
 DISHWASHER AND SINK ARE THE ONLY FIXTURES SERVED HERE.
 IS THIS THE ACTUAL INTENT? IT IS ALSO NOTED THAT THE
 DISHWASHER WHICH IS INDICATED ELSEWHERE IN THE PLANS AS
 A RESIDENTIAL TYPE, SITTING ADJACENT TO THE SINK AND
 DISCHARGING TO THE SANITARY AS A RESIDENTIAL
 DISHWASHER(SEE DETAIL 2), HAS A DEDICATED ? INCH HOT
 WATER SUPPLY. INDICATE IN THE DETAIL WHAT FIXTURE(S)
 AND/OR APPLIANCES ARE SERVED BY THE 110 DEGREE WATER
 FROM THE TMV.
  
 B.DETAIL 6, TYPICAL POINT OF USE HEATER INSTALLATION;
 B1.PER WPB FBC 107.2.1, PROVIDE IN THE DETAIL AN
 APPROVED WATER-TEMPERATURE LIMITING DEVICE THAT
 CONFORMS TO ASSE 1070 OR CSA B125.3; COMPLY WITH FBC PL
 416.5.
  
 10.PLUMBING FIXTURE SCHEDULE;
 SK-1: NOTE 3 REQUIRING ADA COMPLIANCE SHALL APPLY PER
 FBC ACC 212.3.
  
 11.PER FBC PL 604.9, THE FLOW VELOCITY OF THE WATER
 DISTRIBUTION SYSTEM SHALL BE CONTROLLED TO REDUCE THE
 POSSIBILITY OF WATER HAMMER. A WATER-HAMMER ARRESTOR
 SHALL BE INSTALLED WHERE QUICK-CLOSING VALVES ARE
 UTILIZED. WATER-HAMMER ARRESTORS SHALL BE INSTALLED IN
 ACCORDANCE WITH THE MANUFACTURER?S INSTRUCTIONS.
 WATER-HAMMER ARRESTORS SHALL CONFORM TO ASSE 1010. THIS
 IS APPLICABLE TO THE ICE MAKER AND THE DISHWASHER.
  
 A COMPREHENSIVE REVIEW COULD NOT BE ACCOMPLISHED AT
 THIS TIME. PLEASE RESUBMIT CLEARLY LEGIBLE PLANS AND A
 RESPONSE NARRATIVE ADDRESSING THE PLUMBING COMMENTS
 FROM THE PREVIOUS REVIEW.
  
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER