2020-09-23 15:16:141ST REVIEW FBC-2017 MECHANICAL
 PERMIT-20081056
  
 CODES IN EFFECT:
  
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET LS1.0- INDICATES AN OCCUPANCY OF 19 PEOPLE.
 SHEET M3.1 INDICATES 9 OCCUPANTS IN THE VENTILATION
 CALCULATIONS. PLEASE SUBMIT A VENTILATION CALCULATION
 BASED ON THE CODE ANALYSIS OCCUPANT COUNT OF 19 PEOPLE.
 FBC M TABLE 403.3.1.1
  
 2) PLEASE SHOW HOW THE AREA WITH THE MINI SPLITS WILL
 BE PROVIDED THE REQUIRED OUTDOOR AIR. FBC M TABLE
 403.3.1.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
  