| Plan Review Notes For Permit 20081055 |
| Permit Number |
20081055 |
|
| Review Stop |
B |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2020-11-05 14:09:37 | BUILDING REVIEW APPROVED WITH PROVISO: | | | (NOTE: PROVIDE INFORMATION FOR REVIEW PRIOR TO | | | INSPECTIONS): | | | 1- REVISE ENERGY CALCULATIONS: WINDOWS AND DOORS | | | INFORMATION DON'T MATCH PLANS. SEE PLANS AND REVISE AS | | | REQUIRED. | | | 2- REVISE THE CODE DATA INFORMATION SHOWN ON THE | | | INDEX-COVER PAGE: | | | A)THERE IS NOT OCCUPANCY CLASSIFICATION 5B. | | | B)PROPOSED FLOOR PLAN SHOWS WAREHOUSE/OFFICE. REVISE | | | CODE DATA OCCUPANCY CLASSIFICATION TO STORAGE AND | | | BUSINESS (MIXED USE. AND CLEARLY SPECIFY IF STORAGE S-1 | | | OR S-2.) | | | C) CHANGE OF USE. A NEW CERTIFICATE OF OCCUPANCY WILL | | | BE REQUIRED AS REQUIRED BY SEC. 1001.3 FBC-EXISTING | | | BUILDING. |
|