| 2020-11-03 14:25:26 | SECOND BUILDING REVIEW COMMENTS |
| | CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. |
| | |
| | NOTE: |
| | BUILDING REVIEW MAY BE APPROVED WITH PROVISO. PROVISO |
| | MEANS CONTRACTOR WILL SUBMIT REQUIRED INFORMATION AFTER |
| | THE PERMIT IS ISSUED BUT BEFORE INSPECTIONS TO AVOID |
| | CONFLICTS/DELAYS. REVISION FEES MAY APPLY. CONTRACTOR |
| | TO ADVICE IF PROVISO OPTION IS PREFERRED AT THIS TIME |
| | OR IF RE-SUBMITTING REQUIRED INFORMATION BEFORE PERMIT |
| | ISSUANCE. |
| | |
| | ***IMPORTANT*** |
| | ENERGY CALCULATIONS NEED TO BE CERTIFIED BY THE OWNER |
| | OR AUTHORIZED AGENT BEFORE ISSUING THE PERMIT. |
| | |
| | |
| | NOTE: SEC. 702.6 FBC-EXISTING BUILDING. ALL NEW WORK |
| | SHALL COMPLY WITH THE MATERIALS AND METHODS |
| | REQUIREMENTS IN THE FLORIDA BUILDING CODE. |
| | NOTE: SEC. 801.3 FBC-EXISTING BUILDING. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE. |
| | |
| | 1- ENERGY CALCULATIONS SUBMITTED: |
| | A) THE BUILDING'S OWNER, THE OWNER'S ARCHITECT, OR |
| | OTHER AUTHORIZED AGENT LEGALLY DESIGNATED BY THE OWNER |
| | SHALL CERTIFY THAT THE BUILDING IS IN COMPLIANCE WITH |
| | THE CODE, AS PER SECTION 553.907, FLORIDA STATUTES, |
| | PRIOR TO RECEIVING THE PERMIT TO BEGIN CONSTRUCTION OR |
| | RENOVATION AS REQUIRED BY SEC. C103.1.1.2 FBC-ENERGY |
| | CONSERVATION. |
| | |
| | RESPONSE: |
| | ENERGY FORM SUBMITTED DOESN'T HAVE ANY BODY SIGNING |
| | UNDER THE OWNER OR AGENT LINE. |
| | |
| | B) PARTIALLY COMPLIED. ARCHITECT SUBMITTED LETTER |
| | STATING COMPLIANCE. SEC. C103.1.1.2 FBC-ENERGY |
| | CONSERVATION REQUIRES CERTIFICATION ON THE ENERGY CODE |
| | FORM. SEE SEC. C103.1.1.2 FBC-ENERGY CONSERVATION. |
| | |
| | C) WINDOWS AND DOORS INFORMATION DON'T MATCH PLANS. |
| | THERE ARE WINDOWS ON THREE SIDES OF THE BUILDING NOT |
| | JUST ON THE NORTH SIDE. THERE ARE MORE DOORS ON THE |
| | SOUTH SIDE. HOW ARE THE WINDOWS SHADED? SEE PLANS, |
| | ELEVATIONS AND REVISE AS REQUIRED. SEC. C103.2 |
| | FBC-ENERGY CONSERVATION. |
| | |
| | RESPONSE: |
| | NOT ADDRESSED. |
| | |
| | 2- REVISE THE CODE DATA INFORMATION SHOWN ON THE |
| | INDEX-COVER PAGE: |
| | A THE OCCUPANCY CLASSIFICATION IS NOT R2, UNIT 711. |
| | SEC. 302.1 FBC-BUILDING. |
| | |
| | RESPONSE: |
| | OCCUPANCY CLASSIFICATION WAS CHANGED TO 5B. WHAT IS |
| | OCCUPANCY CLASSIFICATION 5B?. INFORMATION IS NOT CLEAR. |
| | 5B IS A CONSTRUCTION TYPE NOT OCCUPANCY TYPE. REVISE AS |
| | REQUIRED. SEC. 107.2.1 CITY AMENDMENTS. |
| | |
| | B)THIS IS NOT A LEVEL 2 ALTERATION. SEE ITEM #3 BELOW |
| | AND REVISE AS REQUIRED. SEC. 506 FBC-EXISTING BUILDING. |
| | SEC. 505 FBC-EXISTING BUILDING. |
| | |
| | RESPONSE: |
| | NOT ADDRESSED. |
| | NOTE: |
| | NEED TO COORDINATE THE CODE DATA WITH ITEM #3. NEED TO |
| | CLARIFY IF THIS IS BUSINESS OCCUPANCY OR MIXED |
| | OCCUPANCY: WAREHOUSE AND OFFICE AS SHOWN ON REVISED |
| | SHEET A1.0. |
| | CLARIFICATION IS REQUIRED FOR PROPER PLAN REVIEW. |
| | |
| | 3- SHEET A1.0: |
| | ACCORDING TO CITY RECORDS AND PBC PROPERTY APPRAISER |
| | THE EXISTING BUILDING IS A WAREHOUSE. THE PROPOSED |
| | FLOOR PLAN SHOWS AN STUDIO AS THE PROPOSED USE. THIS IS |
| | A CHANGE OF OCCUPANCY (SEC. 506 FBC-EXISTING BUILDING) |
| | AND ALTERATION LEVEL 3 (SEC. 505 FBC-EXISTING |
| | BUILDING). PLAN SHOWS AN OPEN STUDIO AND NEW ADA |
| | RESTROOM. PLAN DOESN'T SHOW IF THE ACCESS TO THE NEW |
| | STUDIO IS ACCESSIBLE. IT ONLY SHOWS EXISTING ENTRY |
| | DOOR. PLEASE SHOW HOW THE STUDIO IS ACCESSIBLE FROM THE |
| | STREET. SEC. 206.2.1 FBC-ACCESSIBILITY. |
| | |
| | RESPONSE: |
| | INFORMATION ON THE PROPOSED FLOOR PLAN AND THE CODE |
| | DATA ON THE INDEX-COVER PAGE IS NOT CLEAR. IS THIS A |
| | BUSINESS USE OR MIXED USE WAREHOUSE AND BUSINESS. |
| | CLARIFICATION IS REQUIRED FOR PROPER PLAN REVIEW. |
| | ALSO, CLARIFY IF ENTRY IS ACCESSIBLE. NOTE STATING |
| | "EXISTING THRESHOLD" DOESN'T CLARIFY IF THE THRESHOLD |
| | IS ACCESSIBLE OR NOT. |
| | |
| | 4- OK |
| | |
| | 5- OK |
| | |
| | 6- OK |
| | |
| | 7- OK |
| | |
| | 8- A NEW CERTIFICATE OF OCCUPANCY WILL BE REQUIRED AS |
| | REQUIRED BY SEC. 1001.3 FBC-EXISTING BUILDING. |
| | |
| | WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE |
| | ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF |
| | THE REVISION MADE, IDENTIFYING THE SHEET OR |
| | SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL |
| | HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR |
| | ANTICIPATED COOPERATION. |
| | |
| | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY |
| | QUESTIONS REGARDING THESE COMMENTS, |