Plan Review Notes
Plan Review Notes For Permit 20081055
Permit Number 20081055
Review Stop P
Sequence Number 1
Notes
Date Text
2020-09-03 12:02:2009/03/20 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. A SUB PLUMBING PERMIT IS REQUIRED BY A LICENSED
 CONTRACTOR FOR THE SCOPE OF WORK PER THE WPB AMENDMENTS
 TO THE FBC SEC. 105.1.
  
 2. PLEASE SUBMIT A SLAB REPAIR DETAIL, SHOW THE WIDTH
 OF THE REPAIR, THE MINIMUM THICKNESS OF THE CONCRETE TO
 BE REPLACED, AND THE PSI OF THE CONCRETE. SHOW THE SIZE
 AND LENGTH OF THE DOWELS, THE MINIMUM EMBODIMENT DEPTH
 INTO THE EXISTING SLAB, THE ANCHORING MATERIAL FOR THE
 DOWELS AND THE SPACING OF THE DOWELS ON CENTER. THE
 REPAIR SHALL ALSO INCLUDE TERMITE TREATMENT OF THE SOIL
 AND THE REQUIRED VAPOR BARRIER OVER WELL-COMPACTED
 SOIL. A COPY OF THE TERMITE CERTIFICATE SHALL BE ONSITE
 FOR A FINAL INSPECTION.
  
 3. SIGNED AND SEALED DRAWINGS NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR
 ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW - OR -
 IF YOUR ENGINEER DOES NOT HAVE A ELECTRONIC OR DIGITAL
 SIGNATURE - PLEASE DROP OFF (CITY HALL DROP BOX) THE
 ORIGINAL SIGNED AND SEALED DOCUMENT ALONG WITH A "PLAN
 REVIEW REQUEST FORM" EXPLAINING THE REASON FOR
 SUBMITTING THE DOCUMENT OR DRAWINGS. PLAN REVIEW
 REQUEST FORM CAN BE OBTAINED BY E MAILING [email protected]
 AND ASKING FOR THE FORM.
  
 4. PLEASE IDENTIFY THE USE OF THE SECOND SINK AND ITS
 USE PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 5. WATER HEATER IS NOT IN A LOCATION THAT PROVIDES
 ACCESS FOR OBSERVATION, MAINTENANCE, SERVICING AND
 REPLACEMENT AS THE AC UNIT IS NEXT TO IT BLOCKING IT
 PER THE 2017 FBC SEC. P 501.4 LOCATION.
  
 6. SHEET A1-0;
 A. PLEASE PROVIDE A DETAIL CLEAR FLOOR SPACE FOR LAV
 AND TOILET, WHICH SHALL BE 60 INCHES MINIMUM MEASURED
 PERPENDICULAR FROM THE SIDE WALL AND 56 INCHES MINIMUM
 MEASURED PERPENDICULAR FROM THE REAR WALL PER 2017 FBC
 ACC. SEC. 604.3.1.
  
 B. PLEASE SHOW THE DISTANCE FROM TOILET FOR THE PAPER
 HOLDER PER THE 2017 FBC ACC SEC. 604.7.
  
 C. LAVATORY WATER SUPPLY AND DRAINPIPES UNDER SIDE
 SHALL BE INSULATED OR OTHERWISE CONFIGURED TO PROTECT
 AGAINST CONTACT PER THE 2017 FBC ACC SEC. 606.5.
  
 D. ON THE LABORATORY DETAIL FOR THE MIRROR PLEASE AD
 NOTE ON 40" MAX TO THE REFLECTIVE SIDE PER THE 2017 FBC
 ACC SEC. 603.3.
  
 E. THE FIRST WATER CLOSET DETAIL IS NOT NECESSARY THAT
 THE 24" GRAB BAR BE SHOWN AS IT MAY CAUSE CONFUSION FOR
 INSTALLERS IN FIELD INSTEAD PLEASE GIVE THE DIMENSIONS
 FOR TOILET FROM WALL PER THE 2017 FBC ACC SEC. 604.2
 (A) 16"-18".
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved