| Date |
Text |
| 2020-09-03 12:02:20 | 09/03/20 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1. A SUB PLUMBING PERMIT IS REQUIRED BY A LICENSED |
| | CONTRACTOR FOR THE SCOPE OF WORK PER THE WPB AMENDMENTS |
| | TO THE FBC SEC. 105.1. |
| | |
| | 2. PLEASE SUBMIT A SLAB REPAIR DETAIL, SHOW THE WIDTH |
| | OF THE REPAIR, THE MINIMUM THICKNESS OF THE CONCRETE TO |
| | BE REPLACED, AND THE PSI OF THE CONCRETE. SHOW THE SIZE |
| | AND LENGTH OF THE DOWELS, THE MINIMUM EMBODIMENT DEPTH |
| | INTO THE EXISTING SLAB, THE ANCHORING MATERIAL FOR THE |
| | DOWELS AND THE SPACING OF THE DOWELS ON CENTER. THE |
| | REPAIR SHALL ALSO INCLUDE TERMITE TREATMENT OF THE SOIL |
| | AND THE REQUIRED VAPOR BARRIER OVER WELL-COMPACTED |
| | SOIL. A COPY OF THE TERMITE CERTIFICATE SHALL BE ONSITE |
| | FOR A FINAL INSPECTION. |
| | |
| | 3. SIGNED AND SEALED DRAWINGS NEED TO BE |
| | DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR |
| | ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW - OR - |
| | IF YOUR ENGINEER DOES NOT HAVE A ELECTRONIC OR DIGITAL |
| | SIGNATURE - PLEASE DROP OFF (CITY HALL DROP BOX) THE |
| | ORIGINAL SIGNED AND SEALED DOCUMENT ALONG WITH A "PLAN |
| | REVIEW REQUEST FORM" EXPLAINING THE REASON FOR |
| | SUBMITTING THE DOCUMENT OR DRAWINGS. PLAN REVIEW |
| | REQUEST FORM CAN BE OBTAINED BY E MAILING [email protected] |
| | AND ASKING FOR THE FORM. |
| | |
| | 4. PLEASE IDENTIFY THE USE OF THE SECOND SINK AND ITS |
| | USE PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 5. WATER HEATER IS NOT IN A LOCATION THAT PROVIDES |
| | ACCESS FOR OBSERVATION, MAINTENANCE, SERVICING AND |
| | REPLACEMENT AS THE AC UNIT IS NEXT TO IT BLOCKING IT |
| | PER THE 2017 FBC SEC. P 501.4 LOCATION. |
| | |
| | 6. SHEET A1-0; |
| | A. PLEASE PROVIDE A DETAIL CLEAR FLOOR SPACE FOR LAV |
| | AND TOILET, WHICH SHALL BE 60 INCHES MINIMUM MEASURED |
| | PERPENDICULAR FROM THE SIDE WALL AND 56 INCHES MINIMUM |
| | MEASURED PERPENDICULAR FROM THE REAR WALL PER 2017 FBC |
| | ACC. SEC. 604.3.1. |
| | |
| | B. PLEASE SHOW THE DISTANCE FROM TOILET FOR THE PAPER |
| | HOLDER PER THE 2017 FBC ACC SEC. 604.7. |
| | |
| | C. LAVATORY WATER SUPPLY AND DRAINPIPES UNDER SIDE |
| | SHALL BE INSULATED OR OTHERWISE CONFIGURED TO PROTECT |
| | AGAINST CONTACT PER THE 2017 FBC ACC SEC. 606.5. |
| | |
| | D. ON THE LABORATORY DETAIL FOR THE MIRROR PLEASE AD |
| | NOTE ON 40" MAX TO THE REFLECTIVE SIDE PER THE 2017 FBC |
| | ACC SEC. 603.3. |
| | |
| | E. THE FIRST WATER CLOSET DETAIL IS NOT NECESSARY THAT |
| | THE 24" GRAB BAR BE SHOWN AS IT MAY CAUSE CONFUSION FOR |
| | INSTALLERS IN FIELD INSTEAD PLEASE GIVE THE DIMENSIONS |
| | FOR TOILET FROM WALL PER THE 2017 FBC ACC SEC. 604.2 |
| | (A) 16"-18". |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | LUIS A. CRESPO |
| | PLUMBING PLAN EXAMINER / INSPECTOR |
| | EMAIL: [email protected] OFFICE: 561 805-6720 |
| | |