Plan Review Notes
Plan Review Notes For Permit 20081055
Permit Number 20081055
Review Stop M
Sequence Number 1
Notes
Date Text
2020-09-14 08:53:51THE ENERGY CALCULATIONS SUBMITTED ARE FOR A 1436 SQ.
 FT. RETAIL SPACE. THE PROJECT SUBMITTED SHOWS SEVERAL
 OCCUPANCY USES AND SHOWS THE SQUARE FOOTAGE TO BE 1551.
 PLEASE BE CONSISTANT WITH SHEET LS1.0
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  
2020-09-14 08:39:421ST REVIEW FBC-2017 MECHANICAL
 PERMIT-20081055
  
 CODES IN EFFECT:
  
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE PROVIDE CALCULATIONS OF THE HEATING AND
 COOLING LOADS. FBC EC C403.2
  
 2) PLEASE SHOW THE O.A. DUCT WORK TO RETURN AIR DUCT.
 FBC FS 107.2.1
  
 3) PLEASE SHOW RETURN AIR DUCTWORK. FBC FS 107.2.1
  
 4) PLEASE PROVIDE A VENTILATION CALCULATION BASED ON
 THE OCCUPANCIES LISTED ON LS1.0. FBC M 403
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  