2020-09-21 16:42:54PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE SITE PLAN SHOWS TWO EXISTING OPENINGS IN THE
 WALL THAT ARE TO BE ENCLOSED WITH CONCRETE BLOCK.
 SUBMIT STRUCTURAL DETAILS FOR THE CONCRETE BLOCK IN
 FILL. SPECIFY THE FOOTING, SIZE, STEEL REINFORCING AND
 SPECIFY HOW THE STEEL WILL BE TIED INTO THE EXISTING
 FOOTINGS. SHOW THE VERTICAL REINFORCING AND TIE BEAM,
 SIZE, REINFORCING AND TIE INTO THE EXISTING TIE BEAM AT
 THE TOP OF THE EXISTING WALL. FBC 107.2.1
  
 2) PROVIDE A DETAIL OF THE PROPOSED POOL BARRIER GATE
 AND SECTION OF FENCE SHOWN ON THE SITE PLAN. FBC
 107.2.1
  
 3) FBC 107.2.1 - INFORMATION ON CONSTRUCTION DOCUMENTS.
 ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF
 THE PERSON RESPONSIBLE FOR THE DESIGN.