| 2020-10-19 10:49:11 | 2ND REVIEW FBC-2017 PLUMBING |
| | PERMIT- 20080995 |
| | 10/19/2020 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET P1: THE REQUIRED PLUMBING FIXTURE CALCULATIONS |
| | INDICATE 10 DRINKING FOUNTAINS REQUIRED AND PROVIDED, |
| | HOWEVER IT APPEARS THAT ONLY 9 ARE SHOWN ON THE FLOOR |
| | PLAN- TABLE 403.3 FBC P AND SECTION 211.2 FBC ACC. |
| | |
| | 2) P1: REFER TO SECTIONS 306, 307, AND 602 FBC ACC AND |
| | PROVIDE DRINKING FOUNTAIN INSTALLATION DETAILS AND |
| | ELEVATION VIEWS SHOWING KNEE AND TOE CLEARANCES, SPOUT |
| | HEIGHTS, SPOUT LOCATIONS, AND THE ADA BARRIERS IF |
| | INSTALLED. |
| | |
| | 3) P1: SHOW THE NEW DRINKING FOUNTAIN INSTALLATIONS ARE |
| | IN COMPLIANCE WITH COMPLIANCE WITH SECTION 307.2 |
| | PROTRUSION LIMITS. |
| | OBJECTS WITH LEADING EDGES MORE THAN 27 INCHES (685 MM) |
| | AND NOT MORE THAN 80 INCHES ABOVE THE FINISH FLOOR OR |
| | GROUND SHALL PROTRUDE 4 INCHES MAXIMUM HORIZONTALLY |
| | INTO THE CIRCULATION PATH. |
| | |
| | 4) P1: WATER AND SANITARY RISER DRAWINGS HAVE BEEN |
| | PROVIDED TO SHOW THE PLUMBING FOR THE 3 NEW DRINKING |
| | FOUNTAINS. IT APPEARS THAT ONLY TWO NEW (P3) DRINKING |
| | FOUNTAINS ARE SHOWN IN THE WATER RISER. |
| | |
| | A) PROVIDE A CORRELATING SYMBOL LEGEND FOR THE P |
| | FIXTURES SHOWN IN THE RISER- SECTION 107.2.1 WPB |
| | |
| | B) SHOW THE LOCATIONS OF THE SHUT OFF VALVES FOR THE |
| | NEW FOUNTAINS- SECTION 606.2 |
| | |
| | C) SHOW THE LOCATIONS OF THE REQUIRED WATER HAMMER |
| | ARRESTORS ON WATER PIPES SUPPLYING THE DRINKING |
| | FOUNTAINS- SECTION 604.9 FBC P. |
| | |
| | 5) P1: THE LOCATION OF THE EXISTING WATER HEATER IS NOT |
| | SHOWN ON THE PLUMBING FLOOR PLAN, HOWEVER IT SHOULD BE |
| | NOTED THAT THE RISER DRAWING DOES NOT SHOW A |
| | RECIRCULATION LINE FOR THE SYSTEM. IT APPEARS THAT THE |
| | DEVELOPED LENGTH OF THE SYSTEM MAY EXCEED 50 FT. FROM |
| | THE WATER HEATER TO THE MOST REMOTE OUTLET REQUIRING |
| | HOT OR TEMPERED WATER. PLEASE VERIFY COMPLIANCE WITH |
| | SECTION 607.2 FBC P. |
| | |
| | 6) REFER TO SECTION 468.3.5.6 FBC B- FLOOR DRAINS AND |
| | HOSE BIBBS. PLEASE VERIFY ALL GROUP TOILET ROOMS ARE |
| | PROVIDED WITH AT LEAST ONE FLOOR DRAIN AND ONE EASILY |
| | ACCESSIBLE HOSE BIBB. THE FLOOR SHALL BE SLOPED DOWN TO |
| | THE DRAIN. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |