Plan Review Notes
Plan Review Notes For Permit 20080995
Permit Number 20080995
Review Stop P
Sequence Number 3
Notes
Date Text
2020-10-19 10:49:112ND REVIEW FBC-2017 PLUMBING
 PERMIT- 20080995
 10/19/2020
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET P1: THE REQUIRED PLUMBING FIXTURE CALCULATIONS
 INDICATE 10 DRINKING FOUNTAINS REQUIRED AND PROVIDED,
 HOWEVER IT APPEARS THAT ONLY 9 ARE SHOWN ON THE FLOOR
 PLAN- TABLE 403.3 FBC P AND SECTION 211.2 FBC ACC.
  
 2) P1: REFER TO SECTIONS 306, 307, AND 602 FBC ACC AND
 PROVIDE DRINKING FOUNTAIN INSTALLATION DETAILS AND
 ELEVATION VIEWS SHOWING KNEE AND TOE CLEARANCES, SPOUT
 HEIGHTS, SPOUT LOCATIONS, AND THE ADA BARRIERS IF
 INSTALLED.
  
 3) P1: SHOW THE NEW DRINKING FOUNTAIN INSTALLATIONS ARE
 IN COMPLIANCE WITH COMPLIANCE WITH SECTION 307.2
 PROTRUSION LIMITS.
 OBJECTS WITH LEADING EDGES MORE THAN 27 INCHES (685 MM)
 AND NOT MORE THAN 80 INCHES ABOVE THE FINISH FLOOR OR
 GROUND SHALL PROTRUDE 4 INCHES MAXIMUM HORIZONTALLY
 INTO THE CIRCULATION PATH.
  
 4) P1: WATER AND SANITARY RISER DRAWINGS HAVE BEEN
 PROVIDED TO SHOW THE PLUMBING FOR THE 3 NEW DRINKING
 FOUNTAINS. IT APPEARS THAT ONLY TWO NEW (P3) DRINKING
 FOUNTAINS ARE SHOWN IN THE WATER RISER.
  
 A) PROVIDE A CORRELATING SYMBOL LEGEND FOR THE P
 FIXTURES SHOWN IN THE RISER- SECTION 107.2.1 WPB
  
 B) SHOW THE LOCATIONS OF THE SHUT OFF VALVES FOR THE
 NEW FOUNTAINS- SECTION 606.2
  
 C) SHOW THE LOCATIONS OF THE REQUIRED WATER HAMMER
 ARRESTORS ON WATER PIPES SUPPLYING THE DRINKING
 FOUNTAINS- SECTION 604.9 FBC P.
  
 5) P1: THE LOCATION OF THE EXISTING WATER HEATER IS NOT
 SHOWN ON THE PLUMBING FLOOR PLAN, HOWEVER IT SHOULD BE
 NOTED THAT THE RISER DRAWING DOES NOT SHOW A
 RECIRCULATION LINE FOR THE SYSTEM. IT APPEARS THAT THE
 DEVELOPED LENGTH OF THE SYSTEM MAY EXCEED 50 FT. FROM
 THE WATER HEATER TO THE MOST REMOTE OUTLET REQUIRING
 HOT OR TEMPERED WATER. PLEASE VERIFY COMPLIANCE WITH
 SECTION 607.2 FBC P.
  
 6) REFER TO SECTION 468.3.5.6 FBC B- FLOOR DRAINS AND
 HOSE BIBBS. PLEASE VERIFY ALL GROUP TOILET ROOMS ARE
 PROVIDED WITH AT LEAST ONE FLOOR DRAIN AND ONE EASILY
 ACCESSIBLE HOSE BIBB. THE FLOOR SHALL BE SLOPED DOWN TO
 THE DRAIN.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  