Plan Review Notes
Plan Review Notes For Permit 20080995
Permit Number 20080995
Review Stop P
Sequence Number 2
Notes
Date Text
2020-10-01 16:54:292ND REVIEW FBC-2017 PLUMBING
 PERMIT- 20080995
 10/1//2020
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
 COMMENT #1 FROM THE IST REVEW HAS NOT BEEN COMPLETELY
 ADDRESSED. I HAVE ADDED NOTES TO THE COMMENT BASED ON
 REVIEW OF THE CORRECTED PLANS.
  
 1) SHEETS A-1: THE NOTES UNDER BUILDING BASICS APPEAR
 TO INDICATE EITHER A LEVEL II OR III ALTERATION AS SET
 FORTH IN THE FLORIDA EXISTING BUILDING CODE- 2017 SIXTH
 EDITION. PLEASE REFER TO SECTION 810.1 MINIMUM
 FIXTURES. WHERE THE OCCUPANT LOAD OF THE STORY IS
 INCREASED BY MORE THAN 20 PERCENT, PLUMBING FIXTURES
 FOR THE STORY SHALL BE PROVIDED IN QUANTITIES SPECIFIED
 IN THE FLORIDA BUILDING CODE PLUMBING BASED ON THE
 INCREASED OCCUPANT LOAD. BECAUSE AN EXISTING FLOOR OR
 LIFE SAFETY PLAN WAS NOT PROVIDED IT IS NOT POSSIBLE TO
 TELL IF THERE HAS BEEN AN INCREASE BEYOND THE ALLOWABLE
 20 PERCENT. PLEASE PROVIDE AN EXISTING FLOOR PLAN
 DRAWING AND OCCUPANT LOAD CALCULATIONS FOR THE EXISTING
 AND NEW FLOOR PLANS. REFER TO TABLE 403.3 FBC P AND
 PROVIDE A PLUMBING FIXTURE CALCULATION SCHEDULE THAT
 SHOWS THE REQUIRED AND PROVIDED NUMBER OF PLUMBING
 FIXTURES.
 THE PLUMBING FIXTURE COUNT TABLE DOES NOT INCLUDE THE
 REQUIRED DRINKING FOUNTAINS AND SERVICE SINK- TABLE
 403.3 FBC P. PLEASE NOTE THE PLAN APPEARS TO SHOW
 DEFICIENCY IN THE NUMBER OF DRINKING FOUNTAINS
 PROVIDED. THE FIXTURE COUNT ALSO DOES NOT PROVIDE A
 BREAKDOWN OF MALE, FEMALE, OR UNISEX BATHROOMS, OR
 BREAKDOWN COUNTS FOR BUSINESS AND ASSEMBLY AREAS.
 PLEASE NOTE THE TOTAL OCCUPANCY OF 890 ON SHEET A-3
 DOES NOT INCLUDE THE OCCUPANCY LOADS FOR THE
 MULTI-ASSEMBLY AREAS- SECTION 403.1 FBC P.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  