| 2020-08-27 17:02:10 | 1ST REVIEW FBC-2017 PLUMBING |
| | PERMIT- 20080995 |
| | 8/27/2020 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET A-1: THE NOTES UNDER BUILDING BASICS APPEAR TO |
| | INDICATE EITHER A LEVEL II OR III ALTERATION AS SET |
| | FORTH IN THE FLORIDA EXISTING BUILDING CODE- 2017 SIXTH |
| | EDITION. PLEASE REFER TO SECTION 810.1 MINIMUM |
| | FIXTURES. WHERE THE OCCUPANT LOAD OF THE STORY IS |
| | INCREASED BY MORE THAN 20 PERCENT, PLUMBING FIXTURES |
| | FOR THE STORY SHALL BE PROVIDED IN QUANTITIES SPECIFIED |
| | IN THE FLORIDA BUILDING CODE PLUMBING BASED ON THE |
| | INCREASED OCCUPANT LOAD. BECAUSE AN EXISTING FLOOR OR |
| | LIFE SAFETY PLAN WAS NOT PROVIDED IT IS NOT POSSIBLE TO |
| | TELL IF THERE HAS BEEN AN INCREASE BEYOND THE ALLOWABLE |
| | 20 PERCENT. PLEASE PROVIDE AN EXISTING FLOOR PLAN |
| | DRAWING AND OCCUPANT LOAD CALCULATIONS FOR THE EXISTING |
| | AND NEW FLOOR PLANS. REFER TO TABLE 403.3 FBC P AND |
| | PROVIDE A PLUMBING FIXTURE CALCULATION SCHEDULE THAT |
| | SHOWS THE REQUIRED AND PROVIDED NUMBER OF PLUMBING |
| | FIXTURES. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL/PLUMBING PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | [email protected] |
| | |