| 2020-09-07 11:22:21 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT-20080980 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) THE CODE ANALYSIS INDICATES THIS PROJECT OCCUPATION |
| | CLASSIFICATION GOING FROM AN INSTITUTIONAL TO BUSINESS. |
| | PLEASE PROVIDE VENTILATION CALCULATIONS FOR THIS NEW |
| | CLASSIFICATION FOR THE ENTIRE BUILDING. |
| | |
| | 2) SHEET M0.01: EF-2 DOES NOT SHOW ANY CFM RATES. |
| | PLEASE INDICATE CFM?S EXHAUSTED WITH EF-2. FBC FS |
| | 107.2.1 |
| | |
| | 3) THE EXHAUST DUCTS IN THE RETURN AIR PLENUM MUST |
| | COMPLY WITH: FBC M 601.4 |
| | |
| | 4) PLEASE PROVIDE A MECHANICAL DEMO SHEET AND A NEW |
| | MECHANICAL WORK SHEET. FBC FS 107.2.1 |
| | |
| | 5) SHEET M1.01: PLEASE PROVIDE A SCHEDULE IDENTIFYING |
| | EXISTING, NEW AND THE HASH LINES THROUGH DUCTS. FBC FS |
| | 107.2.1 |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD |
| | SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER |
| | SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN |
| | THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS |
| | PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS |
| | PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR |
| | UPDATED. |
| | |
| | |