| Plan Review Notes For Permit 20080969 |
| Permit Number |
20080969 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2020-10-22 08:47:40 | WINDOW WALL | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected]. | | | CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1 | | | AMENDMENTS | | | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | | 1) REVISED ENGINEERING CALCULATIONS NEED TO BE REVIEWED | | | AND MARKED APPROVED BY THE BUILDING DESIGNER OF RECORD. | | | 2) DRAWING (C-001) NEEDS TO BE REVISED (EXPOSURE C IS | | | STILL SHOWN). BE SURE TO HAVE THE REVISIONS REVIEWED | | | AND MARKED APPROVED BY THE BUILDING DESIGNER OF RECORD. |
|