| 2020-09-11 07:28:22 | PLAN | | | REVIEW COMMENTS | | | FLOORING SOUND INSULATION | | | 1ST REVIEW: FBC SIXTH EDITION (2017) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THE DOCUMENTS THAT WERE SUBMITTED ONLY HAVE THE | | | FLAME SPREAD AND SMOKE DEVELOPED TEST REPORT. SUBMIT | | | THE ACTUAL TEST REPORTS FROM AN APPROVED TESTING | | | FACILITY FOR THE AIR BORNE AND STRUCTURE BORNE SOUND | | | TRANSMISSION FOR THE PROPOSED FLOORING SYSTEM. | | | | | | FBC 1207.2 AIR-BORNE SOUND. ASTM E 90-04 | | | WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES | | | SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM | | | PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION | | | CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) | | | FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM | | | E 90. | | | | | | FBC 1207.3 STRUCTURE-BORNE SOUND. ASTM E 492-09 | | | FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR | | | BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA | | | WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION | | | CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD | | | TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. | | | | | | |
|