| Plan Review Notes For Permit 20080891 |
| Permit Number |
20080891 |
|
| Review Stop |
B |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2021-01-13 10:28:12 | SIGN | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected]. | | | CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1 | | | AMENDMENTS | | | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | | 1) SIGN DESIGN HAS BEEN CHANGED FROM A WALL MOUNTED | | | SIGN TO A CEILING MOUNTED SIGN. SIGN IS SUBJECT TO WIND | | | LOADS PLEASE PROVIDE THE STRUCTURAL CALCULATIONS AND | | | ATTACHMENT DETAILS FOR THE SIGN OR PROVIDE SIGNED AND | | | SEALED ATTACHMENT DETAILS FOR THE "NEW SIGN DESIGN" | | | FROM AN ARCHITECT OR ENGINEER. SHOW THE WIND DESIGN | | | CRITERIA USED FOR DESIGN ON THE DRAWINGS FBC 1609 | | | 2) BE SURE TO HAVE THE NEW DESIGN MARKED APPROVED BY | | | CITY PLACE. | | | |
|