Plan Review Notes
Plan Review Notes For Permit 20080873
Permit Number 20080873
Review Stop B
Sequence Number 1
Notes
Date Text
2020-09-24 10:38:00PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SUBMIT SPEC SHEETS AND INSTALLATION INSTRUCTIONS FOR
 THE PROPOSED STORAGE BATTERIES. FBC 107.2.1
  
 2) PROVIDE A SITE PLAN SHOWING THE SIZE AND LOCATION OF
 THE OUTDOOR BATTERY BANK. FBC 107.1
  
 3) ADDITIONAL COMMENTS MAY RESULT AFTER THE REQUESTED
 INFORMATION IS PROVIDED, SUCH AS, REQUIRED DISTANCE
 FROM OPENINGS INTO A BUILDING, WEATHER PROTECTION FOR
 BATTERIES AND CONNECTIONS, DISPERSION OF HAZARDOUS
 GASES. FBC 107