| 2020-08-20 08:53:12 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT-20080820 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PLEASE PROVIDE THE PRIMARY PERMIT NUMBER ON THE |
| | APPLICATION. FBC FS 107.2.1 |
| | |
| | 2) PLEASE PROVIDE INFORMATION AND SPECS ON THIS WALK IN |
| | COOLER AND COMPRESSOR. FBC FS 107.2.1 |
| | |
| | 3) SHEET AE 106: PLEASE MARK AREA OF WORK ON THE |
| | DRAWING. FBC FS 107.2.1 |
| | |
| | 4) PLEASE PROVIDE REFRIGERANT SYSTEM INFORMATION BASED |
| | ON FBC M 1102.1 |
| | |
| | SECTION1102 |
| | SYSTEM REQUIREMENTS |
| | 1102.1GENERAL. |
| | THE SYSTEM CLASSIFICATION, ALLOWABLE REFRIGERANTS, |
| | MAXIMUM QUANTITY, ENCLOSURE REQUIREMENTS, LOCATION |
| | LIMITATIONS, AND FIELD PRESSURE TEST REQUIREMENTS SHALL |
| | BE DETERMINED AS FOLLOWS: |
| | 1.DETERMINE THE REFRIGERATION SYSTEM'S CLASSIFICATION, |
| | IN ACCORDANCE WITH SECTION 1103.3. |
| | 2.DETERMINE THE REFRIGERANT CLASSIFICATION IN |
| | ACCORDANCE WITH SECTION 1103.1. |
| | 3.DETERMINE THE MAXIMUM ALLOWABLE QUANTITY OF |
| | REFRIGERANT IN ACCORDANCE WITH SECTION 1104, BASED ON |
| | TYPE OF REFRIGERANT, SYSTEM CLASSIFICATION AND |
| | OCCUPANCY. |
| | 4.DETERMINE THE SYSTEM ENCLOSURE REQUIREMENTS IN |
| | ACCORDANCE WITH SECTION 1104. |
| | 5.REFRIGERATION EQUIPMENT AND APPLIANCE LOCATION AND |
| | INSTALLATION SHALL BE SUBJECT TO THE LIMITATIONS OF |
| | CHAPTER 3. |
| | 6.NONFACTORY-TESTED, FIELD-ERECTED EQUIPMENT AND |
| | APPLIANCES SHALL BE PRESSURE TESTED IN ACCORDANCE WITH |
| | SECTION 1108. |
| | |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD |
| | SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER |
| | SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN |
| | THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS |
| | PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS |
| | PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR |
| | UPDATED. |
| | |
| | |