| 2020-08-24 10:14:09 | 08/24/20 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1. THE CLAIMED VALUE APPEARS TO BE UNDERESTIMATED ON |
| | THE APPLICATION, PLEASE PROVIDE A BONA FIDE SIGNED |
| | CONTRACT PER THE WPB AMENDMENTS TO THE FBC SEC. 109.3 |
| | BUILDING PERMIT VALUATIONS. |
| | |
| | 2. ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND |
| | ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF |
| | THE PERSON RESPONSIBLE FOR THE DESIGN PER THE WPB |
| | AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. SIGNED AND SEALED DRAWINGS NEED |
| | TO BE DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER |
| | OR ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW. IT |
| | APPEARS THE MAIN PERMITTED SET HAVE AN ELECTRONIC |
| | SIGNATURE, BUT THESE DONE. |
| | 3. A SUB PLUMBING PERMIT IS REQUIRED BY A LICENSED |
| | CONTRACTOR FOR THE SCOPE OF WORK PER THE WPB AMENDMENTS |
| | TO THE FBC SEC. 105.1. |
| | |
| | 4. IN SHEET C400 IT SHOWS A STORM LINE MOVED TO A |
| | DIFFERENT LOCATION PLEASE CLARIFY IF THIS IS PART OF |
| | THE SCOPE OF WORK OR A REVISION WAS DONE OR WILL BE |
| | NEEDED PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 5. IN SHEET C401 IT SHOWS A WATER LINE FOR FIRE AND NOT |
| | CLEAR IF THIS IS PART OF THE SCOPE OF WORK THAT IS |
| | GOING TO TAKE PLACE. THIS MAY REQUIRE A REVISION AND |
| | FURTHER REVIEW BY THE ENGINEERING DEPARTMENT PLEASE |
| | CLARIFY, THIS FIRE LINE CAN ONLY BE INSTALLED BY A FIR |
| | PREVENTION AND CONTROL LICENSED CONTRACTOR I, II AND V |
| | ACCORDING TO 2017 FLORIDA STATUTES 633.102. |
| | |
| | 6. A GENERAL CONTRACTOR OR AN UNDERGROUND UTILITY AND |
| | EXCAVATION CONTRACTOR CANNOT INSTALL A SEWER PER THE |
| | 2019 FLORIDA STATUTES TITLE XXXII CHAPTER 489.105(N). |
| | PLEASE PROVIDE THE PERMITTING DEPARTMENT WITH A VALID |
| | STATE OF FLORIDA LICENSED CONTRACTOR ALONG WITH AN |
| | APPLICATION. |
| | |
| | FS 489.105 DEFINITIONS.-- AS USED IN THIS PART: |
| | (1) "BOARD" MEANS THE CONSTRUCTION INDUSTRY LICENSING |
| | BOARD. |
| | (2) "DEPARTMENT" MEANS THE DEPARTMENT OF BUSINESS AND |
| | PROFESSIONAL REGULATION. |
| | (3) "CONTRACTOR" MEANS THE PERSON WHO IS QUALIFIED FOR, |
| | AND IS ONLY RESPONSIBLE FOR, THE PROJECT. |
| | |
| | (N) "UNDERGROUND UTILITY AND EXCAVATION CONTRACTOR" |
| | MEANS A CONTRACTOR WHOSE SERVICES ARE LIMITED TO THE |
| | CONSTRUCTION, INSTALLATION, AND REPAIR, ON PUBLIC OR |
| | PRIVATE PROPERTY, WHETHER ACCOMPLISHED THROUGH OPEN |
| | EXCAVATIONS OR THROUGH OTHER MEANS, INCLUDING, BUT NOT |
| | LIMITED TO, DIRECTIONAL DRILLING, AUGER BORING, JACKING |
| | AND BORING, TRENCHLESS TECHNOLOGIES, WET AND DRY TAPS, |
| | GROUTING, AND SLIP LINING, OF MAIN SANITARY SEWER |
| | COLLECTION SYSTEMS, MAIN WATER DISTRIBUTION SYSTEMS, |
| | STORM SEWER COLLECTION SYSTEMS, AND THE CONTINUATION OF |
| | UTILITY LINES FROM THE MAIN SYSTEMS TO A POINT OF |
| | TERMINATION UP TO AND INCLUDING THE METER LOCATION FOR |
| | THE INDIVIDUAL OCCUPANCY, SEWER COLLECTION SYSTEMS AT |
| | PROPERTY LINE ON RESIDENTIAL OR SINGLE-OCCUPANCY |
| | COMMERCIAL PROPERTIES, OR ON MULTIOCCUPANCY PROPERTIES |
| | AT MANHOLE OR WYE LATERAL EXTENDED TO AN INVERT |
| | ELEVATION AS ENGINEERED TO ACCOMMODATE FUTURE BUILDING |
| | SEWERS, WATER DISTRIBUTION SYSTEMS, OR STORM SEWER |
| | COLLECTION SYSTEMS AT STORM SEWER STRUCTURES. HOWEVER, |
| | AN UNDERGROUND UTILITY AND EXCAVATION CONTRACTOR MAY |
| | INSTALL EMPTY UNDERGROUND CONDUITS IN RIGHTS-OF-WAY, |
| | EASEMENTS, PLATTED RIGHTS-OF-WAY IN NEW SITE |
| | DEVELOPMENT, AND SLEEVES FOR PARKING LOT CROSSINGS NO |
| | SMALLER THAN 2 INCHES IN DIAMETER IF EACH CONDUIT |
| | SYSTEM INSTALLED IS DESIGNED BY A LICENSED PROFESSIONAL |
| | ENGINEER OR AN AUTHORIZED EMPLOYEE OF A MUNICIPALITY, |
| | COUNTY, OR PUBLIC UTILITY AND THE INSTALLATION OF SUCH |
| | CONDUIT DOES NOT INCLUDE INSTALLATION OF ANY CONDUCTOR |
| | WIRING OR CONNECTION TO AN ENERGIZED ELECTRICAL SYSTEM. |
| | AN UNDERGROUND UTILITY AND EXCAVATION CONTRACTOR MAY |
| | NOT INSTALL PIPING THAT IS AN INTEGRAL PART OF A FIRE |
| | PROTECTION SYSTEM AS DEFINED IN S. 633.102 BEGINNING AT |
| | THE POINT WHERE THE PIPING IS USED EXCLUSIVELY FOR SUCH |
| | SYSTEM. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | LUIS A. CRESPO |
| | PLUMBING PLAN EXAMINER / INSPECTOR |
| | EMAIL: [email protected] OFFICE: 561 805-6720 |
| | |