| 2020-08-20 16:28:32 | 08/20/20 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1. A SUB PLUMBING PERMIT IS REQUIRED PER THE WPB |
| | AMENDMENTS TO THE FBC SEC. 105.1. |
| | |
| | 2. SHEET A000 ACCESSIBILITY; |
| | |
| | A. UNDER FAC NOTES LETTER H TOILET PAPER DISPENSER |
| | VERBIAGE SHALL BE PER THE 2017 ACC 604.7. |
| | |
| | B. UNDER FAC NOTES LETTER N THE MIRROR SHALL BE 40" TO |
| | THE REFLECTIVE PART PER THE 2017 FBC ACC SEC. 603.3. |
| | |
| | C. IN DETAIL OF THE SECTION 606.3 THE MIRROR NEEDS TO |
| | BE NOTED TO THE REFLECTIVE PART OF IT PER THE 2017 FBC |
| | ACC SEC. 603.3. |
| | |
| | D. IN THAT SAME DETAIL THE NOTE FOR HOT WATER PIPING |
| | WRAP SHOULD BE REEFING 2017 FBC ACC SEC. 606.5. |
| | |
| | E. PLEASE DELETE ANY VERBIAGE OR DRAWINGS THAT DOES NOT |
| | REFLECT OF COINCIDE WITH THIS PROJECT ON ALL PLUMBING |
| | PAGES, I.E., DRINKING FOUNTAIN, KITCHEN SINK, URINAL, |
| | ETC., PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 3. SHEET A100 ACCESSIBILITY; |
| | |
| | A. IN CONSTRUCTION PLANS PLEASE SHOW ALL DIMENSIONS FOR |
| | ALL DETAIL OF CLEAR FLOOR SPACE LAV AND TOILET PER THE |
| | WPB AMENDMENTS TO THE FBC SEC. 107.2.1. INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. |
| | |
| | B. PLEASE DELETE ANY VERBIAGE OR DRAWINGS THAT DOES NOT |
| | REFLECT OF COINCIDE WITH THIS PROJECT ON ALL PLUMBING |
| | PAGES PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 4. SHEET P-2 PLUMBING; |
| | |
| | A. PLEASE PROVIDE SPECIFICATIONS FOR INSTA-HOT FROM |
| | MANUFACTURE PER THE WPB AMENDMENTS TO THE FBC SEC. |
| | 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | B. STOPS ON THE SINK DETAIL SHOWS ONLY ONE ANGLE STOP |
| | NOTED AS THREE WAY PLEASE SHOW INDIVIDUAL STOP FOR EACH |
| | FIXTURE PER THE 2017 FBC P 606.3. |
| | |
| | C. PLEASE DELETE ANY VERBIAGE OR DRAWINGS THAT DOES NOT |
| | REFLECT OF COINCIDE WITH THIS PROJECT ON ALL PLUMBING |
| | PAGES PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | LUIS A. CRESPO |
| | PLUMBING PLAN EXAMINER / INSPECTOR |
| | EMAIL: [email protected] OFFICE: 561 805-6720 |
| | |