| 2020-09-07 20:43:23 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. PROVIDE LOCATIONS OF EXISTING SERVICE DISC MB PANEL |
| | AND NEW SERVICE DISC 125AMP MB PANEL TO BE INSTALLED. |
| | MAINS MUST BE GROUPED NEC 230.72A FBC 107.2.1 |
| | |
| | 2. PROVIDE LOAD CALCULATION FOR EXISTING SERVICE TO |
| | INCLUDE NEW AND EXISTING LOADS (INCLUDING NEW 125AMP MB |
| | PANEL). SHOW SIZE OF EXISTING SERVICE ENTRANCE |
| | CONDUCTORS AND THAT THEY ARE OF SUFFICIENT SIZE. NEC |
| | 220 FBC 107.2.1 |
| | |
| | 3. WHAT SIZE IS METERCAN? |
| | |
| | 4. NO GROUNDING ELECTRODE SYSTEM CONNECTION SHOWN AT |
| | NEW 125AM MB PANEL? |
| | |
| | 5. PANEL WITH 125AMP BUSBAR CANNOT BE BACKFED BY 125AMP |
| | SOLAR BACKFED BREAKER. NEC 690.10(E), 705.12(D)(2)(#3 |
| | A,B) |
| | |
| | |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | CODES IN EFFECT: |
| | |
| | IF THE RESUBMITTAL IS NOT PREPARED BY A DESIGN |
| | PROFESSIONAL (ARCHITECT OR ENGINEER), AND THE PAGES ARE |
| | 11X17 OR SMALLER, YOU MAY RESUBMIT, ALONG WITH A |
| | COMPLETED RESUBMITTAL FORM, VIA EMAIL TO |
| | [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT |
| | NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE |
| | RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE: |
| | |
| | HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B |
| | UILDING-PERMIT-FORMS |
| | |
| | |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE 2017 6TH ED. |
| | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| | 6TH EDITION |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | V/R, |
| | |
| | FRANK GIAQUINTO III |
| | ELECTRICAL INSPECTOR |
| | ELECTRICAL PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | [email protected] |
| | CELL: 561-657-1653 |
| | |