| 2020-08-20 15:03:13 | 1ST REVIEW FBC-2017 RES. |
| | PERMIT- 20080726 |
| | 8/20/2020 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| | EDITION 2017 |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) THE GAS ISOMETRIC SHOWS THE NEW PIPING TO THE |
| | GENERATOR IN COMPLIANCE, HOWEVER THE EXISTING GAS |
| | PIPING SHOWN FROM THE NEW REGULATOR AT 12" WC IS |
| | UNDERSIZED PER SECTIONS G2413.2, G2413.3, G2413.4, & |
| | G2413.4.1 FBC RES. |
| | |
| | A) USING THE LONGEST LENGTH METHOD, THE TOTAL DEVELOPED |
| | LENGTH OF THE SYSTEM IS 142 FT. FROM THE NEW REGULATOR |
| | TO THE MOST REMOTE OUTLET (BBQ). THE TOTAL LOAD OF THE |
| | SYSTEM IS 610 BTUH. BASED ON TABLE G2413.1 THE PIPE RUN |
| | FROM THE REGULATOR TO THE TEE, THE 12 FT. BRANCH LENGTH |
| | OF 1-INCH GALVANIZED PIPE RUN UP THE HOUSE WALL (277 |
| | BTUH LOAD), AND THE 21 FT. BRANCH LENGTH OF PIPE RUN TO |
| | THE POOL HEATER (333 BTUH LOAD) SHALL EACH BE MINIMUM |
| | 1-1/4 INCHES. |
| | BASED ON TABLE G2413.4(16) THE 70 FT. LENGTH OF 1-INCH |
| | CSST (277 BTUH LOAD) SHALL BE SIZED AT A MINIMUM 39 |
| | EHD, AND ALL PIPES DOWNSTREAM OF THE CSST WILL HAVE TO |
| | INCREASE IN SIZE ACCORDING TO THE TABLES. PLEASE SUBMIT |
| | A CORRECT ISOMETRIC DRAWING. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL/PLUMBING PLANS EXAMINER |
| | 401 CLEMATIS |
| | |