| Plan Review Notes For Permit 20080703 |
| Permit Number |
20080703 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2020-10-16 08:16:24 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | FLORIDA BUILDING CODE 2017 6TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | | NFPA 70 2014 EDITION | | | | | | JAKE LEAHY BN, BU, PX | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | 1) WIRE SIZE GOING TO JOCKEY PUMP NOT PER 230.31 | | | | | | 230.31 SIZE AND RATING (A) GENERAL. UNDERGROUND SERVICE | | | CONDUCTORS SHALL HAVE SUFFICIENT AMPACITY TO CARRY THE | | | CURRENT FOR THE LOAD AS CALCULATED IN ACCORDANC E WITH | | | ARTICLE 220 AND S HALL HAVE ADEQUATE MECHANICAL | | | STRENGTH. (B) MINIMUM SIZE. THE CONDUCTORS SHALL NOT BE | | | SMALLER THAN 8 AWG COPPER OR 6 AWG ALUMINUM OR | | | COPPER-CLAD ALUMINUM. | | | | | | 2) NEED TO SHOW WIRE SIZES IN GUTTER. |
|