Plan Review Notes
Plan Review Notes For Permit 20080703
Permit Number 20080703
Review Stop E
Sequence Number 1
Notes
Date Text
2020-10-16 08:16:24ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1) WIRE SIZE GOING TO JOCKEY PUMP NOT PER 230.31
  
 230.31 SIZE AND RATING (A) GENERAL. UNDERGROUND SERVICE
 CONDUCTORS SHALL HAVE SUFFICIENT AMPACITY TO CARRY THE
 CURRENT FOR THE LOAD AS CALCULATED IN ACCORDANC E WITH
 ARTICLE 220 AND S HALL HAVE ADEQUATE MECHANICAL
 STRENGTH. (B) MINIMUM SIZE. THE CONDUCTORS SHALL NOT BE
 SMALLER THAN 8 AWG COPPER OR 6 AWG ALUMINUM OR
 COPPER-CLAD ALUMINUM.
  
 2) NEED TO SHOW WIRE SIZES IN GUTTER.