| 2020-08-17 07:16:22 | 08/17/20 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1. THE FILTER ON PLANS CALLS OUT A CC200 AND THE |
| | SUBMITTED SPECS DOES NOT HAVE THAT MODEL LISTED, PLEASE |
| | PROVIDE ONE THE DOES PER THE WPB AMENDMENTS TO THE FBC |
| | SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 2. THE HEATER SHOWN ON PLANS CALLS OUT FOR A T135 MODEL |
| | AND THE ONE SUBMITTED DOES NOT MATCH THAT, PLEASE |
| | PROVIDE ONE THE DOES PER THE WPB AMENDMENTS TO THE FBC |
| | SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 3. THE SUBMITTED POOL PUMP CURVE DOES NOT IDENTIFY THE |
| | PUMP CURVE PLEASE SPECIFY WHICH CURVE KEY IS SPECIFIC |
| | TO THE PUMP BEING INSTALLED ON THIS POOL, SHOW IT ON |
| | THE CURVE. THIS IS NEEDED TO CONFIRM THE MAXIMUM SYSTEM |
| | FLOW FROM THE TDH CALCULATIONS PER THE ANSI/APSP/ICC 7 |
| | - 2013 SECS. 4.4.9, 4.4.9.1. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | LUIS A. CRESPO |
| | PLUMBING PLAN EXAMINER / INSPECTOR |
| | EMAIL: [email protected] OFFICE: 561 805-6720 |
| | |