2020-08-18 15:05:01CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 NFPA 54 = NATIONAL FUEL GAS CODE
 NFPA 58 = LIQUIFIED PETROLEUM GAS CODE
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 20080653 2921 N AUSTRALIAN AVE
  
 A PLUMBING PERMIT IS REQUIRED
 RECORDS (SEE MASTER PERMIT 19070042) INDICATE THAT THE
 LAST RECORDED LOCATION OF AND TYPE OF WATER HEATER IS
 AN ELECTRIC TANK TYPE WATER HEATER LOCATED WELL INTO
 THE INTERIOR OF THE BUILDING. PER CONVERSATION WITH THE
 PERMIT APPLICANT, APPLICATION IS BEING MADE FOR PROPANE
 TANKS AND PIPING TO CONNECT TO GAS TANK-LESS WATER
 HEATER FURNISHED AND INSTALLED BY OTHERS ON THE
 EXTERIOR OF THE BUILDING. THERE DOES NOT APPEAR TO BE A
 PLUMBING PERMIT APPLIED FOR THIS. PER WPB FBC 105.1, A
 PLUMBING PERMIT IS REQUIRED FOR THE PIPING AND
 INSTALLATION OF THE NEW GAS TANK-LESS WATER HEATER.
 PROVIDE PAN VIEW AND RISER DIAGRAM AS WELL AS
 MANUFACTURER?S SPECIFICATION/INSTALLATION MANUAL AS
 REQUIRED IN ACCORDANCE WITH WPB FBC 107.2.1 AND
 107.3.5.1.3.
  
  
 GAS COMMENTS: DENIED
 1. TABLE PROVIDED 402.4(35) IS FOR PE AT 11 INCH WC AND
 THERE DOES NOT APPEAR TO BE ANY PIPING IN THE SYSTEM
 THAT MEETS THAT CRITERIA.PER WPB FBC 107.2.1, PROVIDE
 THE FOLLOWNG:
 A. MANUFACTURER?S DATA/TABLE FOR 10 PSI PE PIPING (NONE
 SHOWN IN FBC FG OR NFPA 54)
 B. TABLE FOR 10 PSI GALVANIZED PIPING
 C. TABLE FOR GALVANIZED PIPING AT 11 INCH WC
  
 2. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS /
 INSTALLATION MANUAL FOR TANKLESS WATER HEATER TO VERIFY
 COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND FBC FG
 402.2 AND 301.3. GAS APPLIANCES SHALL BE LISTED AND
 LABELED. THE INSTALLATION MANUALS FOR ALL GAS
 APPLIANCES / EQUIPMENT SHALL BE ONSITE AT THE TIME OF
 INSPECTION. FGC SEC.305.1, FBC-RES. SEC.G2408.1.
 3. SUBMIT MANUFACTURER?S SPECIFICATIONS FOR THE
 PRESSURE REGULATORS. REGULATORS INSTALLED ON THE
 EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR
 INSTALLATION PER FGC FG 410.1.
 4. ABOVE GROUND TANK ENGINEERING ANCHOR SPEC DOCUMENT
 SHALL BEAR FLORIDA PE SIGNED STAMP/SEAL.
 5. ANCHOR SPECS FOR STORAGE SHED DO NOT REFLECT TANK
 TIE DOWN. PER WPB FBC 107.2.1, CLARIFY.
 6. PER FBC FG 407.17.3, A YELLOW INSULATED COPPER
 TRACER WIRE OR OTHER APPROVED CONDUCTOR SHALL BE
 INSTALLED ADJACENT TO UNDERGROUND NONMETALLIC PIPING.
 ACCESS SHALL BE PROVIDED TO THE TRACER WIRE OR THE
 TRACER WIRE SHALL TERMINATE ABOVE GROUND AT EACH END OF
 THE NONMETALLIC PIPING. THE TRACER WIRE SIZE SHALL BE
 NOT LESS THAN 18 AWG AND THE INSULATION TYPE SHALL BE
 SUITABLE FOR DIRECT BURIAL.
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
 ALL PLANS TO BE SIGNED AND SEALED BY THE DESIGNER AS
 REQUIRED BY FAC AND FS.
 ALL PLANS TO BE DIGITALLY SIGNED AND SEALED BY THE
 DESIGNER IN ACCORDANCE WITH FAC AND FS.
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-246-0882 MOBILE
  
 20080653 2921 N AUSTRALIAN AVE
  