| Plan Review Notes For Permit 20080593 |
| Permit Number |
20080593 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2020-08-13 14:42:52 | A BETTER, MORE DETAILED SITE PLAN IS NEEDED. | | | | | | PLEASE INCLUDE THE DIMENSIONS OF THE TENT, THE | | | SIDEWALK, HOW MANY TABLES, HOW MANY CHAIRS, WHAT IS THE | | | WIDTH OF THE REMAINING SIDEWALK FOR PEDESTRIAN TRAVEL, | | | ANY EXIT DOORS IN THE AREA, ETC. | | | | | | THERE IS AN INDICATION ON THE APPLICATION OF FIWE, | | | PLEASE DEFINE THIS? | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|