| 2020-08-13 09:43:13 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT-20080566 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| | EDITION 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PLEASE PROVIDE A SURVEY INDICATING LOCATION OF |
| | UNDERGROUND LP GAS TANK AND GENERATOR LOCATION ON THIS |
| | PROPERTY. FBC FS 107.2.1 |
| | |
| | 2) PROVIDE A GAS RISER DIAGRAM FOR THIS PROJECT, IT |
| | SHOULD INCLUDE REGULATORS AND PRESSURES OF EACH ALONG |
| | WITH SHUT OFF VALVES LOCATIONS, UNION FITTINGS, DRIP |
| | LEGS, AND PIPING MATERIAL AND LENGTHS. FBC FS 107.2.1 |
| | |
| | 3) PLEASE MARK REGULATORS USED ON THE SUBMITTED |
| | REGULATOR SPECS. FBC FS 107.2.1 |
| | |
| | 4) PLEASE MARK SIZE USED OF THE ANODELESS RISERS SPECS |
| | PROVIDED IN THIS SUBMITTAL. FBC FS 107.2.1 |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD |
| | SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER |
| | SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN |
| | THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS |
| | PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS |
| | PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR |
| | UPDATED. |
| | |
| | |