| 2020-09-14 06:18:43 | 1ST REVIEW FBC-2017 PLUMBING |
| | PERMIT-20080564 |
| | 9/14/2020 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1. GAS PLAN REVIEW, A GAS PLAN HAS NOT BEEN INCLUDED IN |
| | THIS SUBMITTAL PACKAGE. A GAS PLAN REVIEW HAS NOT BEEN |
| | PERFORMED AT THIS TIME. A SEPARATE GAS PERMIT AND PLANS |
| | WILL BE REQUIRED FOR A CONTRACTOR TO PERFORM THE |
| | RELATED WORK. PROVIDE COMPLETE PLANS AND GAS RISER THAT |
| | REFLECTS THE ENTIRE SCOPE OF GAS WORK TO BE DONE. AT |
| | THIS TIME. WPB AMENDMENTS TO FBC SEC. 107.2.1. |
| | |
| | 2. A PORTION OF SHEET S2 IS ILLEGIBLE. SUBMIT A COPY OF |
| | CLEAR AND LEGIBLE PLANS FOR REVIEW. WPB AMENDMENTS TO |
| | THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION |
| | DOCUMENTS. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |