| 2020-08-25 18:09:32 | 08/25/20 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1. THE WATER HEATER ON YOUR FLORIDA ENERGY EFFICIENCY |
| | FORM R405-2017 IS SHOWING THE E.F AS .92. AS OF APRIL |
| | 16, 2015, ALL RESIDENTIAL WATER HEATERS ARE REQUIRED TO |
| | BE A MIN .95 E.F UP TO 55 GALLONS. THIS IS DEFINED IN |
| | THE CODE OF FEDERAL REGULATION (CFR) 75 FR 2012. IF YOU |
| | ARE USING THE TANK TYPE THE PLANS SHOW A TANKLESS WATER |
| | HEATER, PLEASE CLARIFY AND OR MAKE CHANGES PER THE WPB |
| | FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 2. THE TANKLESS REQUIRES CLEARANCE PER MANUFACTURES |
| | INSTALLATION INSTRUCTION SOME WARE WHERE IT CAN BE |
| | REACHED AND BE DUST FREE. IT IS IN A PLENUM WHICH IT |
| | MAY BE DIFFICULT TO OPERATE, SHUTOFF AND SERVICE, |
| | PLEASE PROVIDE AN ALTERNATE LOCATION. |
| | |
| | 3. HOT WATER NOTE D FOR INSULATION NEEDS TO HAVE |
| | VERBIAGE "IF RAN UNDER SLAB IT MUST BE INSULATED WITH A |
| | MINIMUM R-3 INSULATION PER THE 2017 FBC RE 403.5.3." |
| | |
| | 4. A SUB PLUMBING PERMIT IS REQUIRED BY A LICENSED |
| | CONTRACTOR FOR THE SCOPE OF WORK PER THE WPB AMENDMENTS |
| | TO THE FBC SEC. 105.1. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | LUIS A. CRESPO |
| | PLUMBING PLAN EXAMINER / INSPECTOR |
| | EMAIL: [email protected] OFFICE: 561 805-6720 |
| | |