| Plan Review Notes For Permit 20080557 |
| Permit Number |
20080557 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2020-08-12 10:59:54 | RESIDENTIAL (R3) MECHANICAL REVIEW COMMENTS | | | CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. | | | | | | 1- FLOOR PLAN SHOWS AN 8" RETURN AIR DUCT. THE RETURN | | | AIR DUCT SIZE SHOWN ON THE FLOOR PLAN NEEDS TO BE AT | | | LEAST 10" AS REQUIRED BY SEC. M1602.3 EXCEPTION #1. | | | REVISE AS REQUIRED. | | | | | | 2- PROVIDE THE NAME AND SIGNATURE OF THE PERSON | | | RESPONSIBLE FOR THE DESIGN AS REQUIRED BY SEC. 107.2.1 | | | CITY AMENDMENTS. | | | | | | 3- THE MECHANICAL WORK WAS NOT INCLUDED IN THE MASTER. | | | PLEASE COMPLETE THE ATTACHED REVISION FORM AND INCLUDE | | | THE ADDITIONAL VALUE FOR THE MECHANICAL WORK. REVISION | | | FEES WILL BE ADJUSTED ACCORDINGLY. SEC. 109.3 CITY | | | AMENDMENTS. | | | | | | | | | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY | | | QUESTIONS REGARDING THESE COMMENTS, | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] | | | |
|