| Plan Review Notes For Permit 20080536 |
| Permit Number |
20080536 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2020-09-28 11:24:34 | PLAN | | | REVIEW COMMENTS | | | | | | 2ND REVIEW: FBC SIXTH EDITION (2017) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THE ANCHOR SPACING TABLE IN THE CORRUGATED PANEL | | | SCHEDULE ON PAGE 2 OF 10 ON THE PRODUCT APPROVAL FOR | | | THE CLEAR PANELS HAS THE SPANS AND PRESSURES FOR 13" | | | SPACING. I DO NOT SEE ANYTHING THAT ALLOWS HIGHER | | | PRESSURES FOR CLOSER ANCHOR SPACING. BASED ON THE TABLE | | | THE PANELS WITH THE 108" SPAN ARE ONLY GOOD FOR 35 PSF | | | AND THE PANELS SPANNING 128" ARE ONLY GOOD FOR 30 PSF. | | | THESE PRESSURES ARE TOO LOW FOR THESE OPENINGS. FBC | | | 107.2.1 & FBC-R301.2.1.2 | | | | | | |
|