| Plan Review Notes For Permit 20080535 |
| Permit Number |
20080535 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2020-09-02 08:06:16 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | FLORIDA BUILDING CODE 2017 6TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | | NFPA 70 2014 EDITION | | | | | | JAKE LEAHY BN, BU, PX | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | | | | SHOW HOW TERMINATIONS FOR THE 2/0 MEETS THE | | | REQUIREMENTS ON 110.14(C)(1)(B) , A 2/0 AT 75 DEGREES | | | IS ONLY GOOD FOR 175 AND CAN NOT BE PROTECTED BY A 200A | | | FUSE OR BREAKER. | | | | | | 110.14(C)(1)(B) TERMINATION PROVISIONS OF EQUIPMENT FOR | | | CIRCUITS RATED OVER 100 AMPERES, OR MARKED FOR | | | CONDUCTORS LARGER THAN 1 AWG, SHALL BE USED ONLY FOR | | | ONE OF THE FOLLOWING: (1) CONDUCTORS RATED 75?C (167?F) | | | (2) CONDUCTORS WITH HIGHER TEMPERATURE RATINGS, | | | PROVIDED THE AMPACITY OF SUCH CONDUCTORS DOES NOT | | | EXCEED THE 75?C (167?F) AMPACITY OF THE CONDUCTOR SIZE | | | USED, OR UP TO THEIR AMPACITY IF THE EQUIPMENT IS | | | LISTED AND IDENTIFIED FOR USE WITH SUCH CONDUCTORS |
|