| Notes |
| Date |
Text |
| 2020-08-21 14:44:11 | PETER E VALENTI | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6673 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | FBC M = FBC MECHANICAL | | | | | | MECHANICAL REVIEW DENIED: | | | | | | 1) FBC B & WPB AMENDMENTS 107.2.1, PROVIDE, ON NEW | | | PLANS FOR PROPOSED WORK, THE SIGNATURES OF THE PERSON | | | RESPONSIBLE FOR THE DESIGN. WHEN THE PERSON RESPONSIBLE | | | FOR THE SUBMITTED DRAWINGS IS A DESIGN PROFESSIONAL | | | THAT PERSON NEEDS TO PROVIDE SIGNATURES AND SEALS AS | | | PER F.S. 471 AMD 481. | | | 2) FBC R M 1401.4, PROVIDE SIGNED AND SEALED ENGINEER | | | APPROVED TIE DOWN DETAILS FOR BOTH EXTERIOR CONDENSING | | | UNITS. | | | 3) FBC B 107, PROVIDE THE MANUFACTURER'S SPECIFICATIONS | | | FOR ALL NEW UNITS INCLUDING THE MINI-SPLITS WITH (3) | | | AIR HANDLERS AND (1) CONDENSING UNIT. |
|