| 2020-08-26 17:19:57 | 08/26/20 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS | | | | | | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS | | | TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE | | | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. | | | | | | 1. A SUB PLUMBING PERMIT IS REQUIRED BY A LICENSED | | | CONTRACTOR FOR THE SCOPE OF WORK PER THE WPB AMENDMENTS | | | TO THE FBC SEC. 105.1. | | | | | | 2. ON SHEET 300 PLEASE SHOW BOTH CLEANOUTS ON ISOMETRIC | | | DRAWING PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 | | | INFORMATION ON CONSTRUCTION DOCUMENTS. | | | | | | 3. WATER RUNNING UNDER SLAB MUST BE INSULATED WITH AN | | | R-3 PER 2017 FBC SEC. RE 403.5.3. | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & | | | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS | | | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL | | | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE | | | REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO | | | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED | | | COOPERATION. | | | | | | LUIS A. CRESPO | | | PLUMBING PLAN EXAMINER / INSPECTOR | | | EMAIL: [email protected] OFFICE: 561 805-6720 | | | |
|