| 2020-08-26 17:38:41 | 08/26/20 1ST GAS REVIEW**DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1. A SUB GAS PERMIT IS REQUIRED BY A LICENSED |
| | CONTRACTOR FOR THE SCOPE OF WORK PER THE WPB AMENDMENTS |
| | TO THE FBC SEC. 105.1. |
| | |
| | 2. SHOWS THE LENGTH OF ALL CUT SECTIONS OF PIPE PER |
| | 2017 FBC RES. SECS. G2413.4.1, G2413.4.2. |
| | |
| | 3. SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, ALL |
| | PIPE SIZES, FOR EACH PIPE SIZE ON ISOMETRIC PER THE WPB |
| | AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. |
| | |
| | 4. MOST TANKLESS UNIT CALL FOR 10.5" WATER COLUMN AND |
| | THE SERVICE METER DISCHARGES IS A 2 PSI REQUIRING A |
| | REGULATOR FOR THIS UNIT AS PER MANUFACTURER'S |
| | SPECIFICATION. SUBMIT MANUFACTURER'S SPECIFICATIONS FOR |
| | THE PRESSURE REGULATORS. REGULATORS INSTALLED ON THE |
| | EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR |
| | INSTALLATION PER THE 2017 FBC RES. SEC. G2421.1. |
| | 5. SUBMIT CALCULATIONS FOR COMBUSTION AIR FOR STOVE PER |
| | THE FBC RES. SEC. G2407.1 AND G2439.4 |
| | |
| | 6. SUBMIT MANUFACTURER'S SPECIFICATION |
| | SHEETS/INSTALLATION MANUAL FOR STOVE AND TANKLESS |
| | HEATER EQUIPMENT TO VERIFY COMPLIANCE WITH 2017 FBC |
| | RES. SEC. G2408.1. |
| | |
| | 7. PLEASE LABEL AND SHOW ALL UNIONS IN FRONT OF |
| | REGULATOR 1' OF EITHER SIDE PER THE 2017 FBC RES. SEC |
| | G2421.2 OR 2017 FBC FG SEC 410.2. |
| | |
| | 8. PLEASE LABEL THE SHUTOFF VALVE ON GAS ISOMERIC PER |
| | THE 2017 FBC RES. SEC. G2401.1.3. |
| | |
| | 9. PLEASE SHOW AND LABEL DRIP LEG ON EQUIPMENT |
| | INSTALLED PER THE 2017 FBC RES. SEC. G2419. |
| | |
| | 10. IF THIS UNIT REQUIRES CONDENSATE IT MUST BE 1' AWAY |
| | FROM STRUCTURE PER THE 2017 FBC SEC R318.5. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |