2020-08-26 17:38:4108/26/20 1ST GAS REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. A SUB GAS PERMIT IS REQUIRED BY A LICENSED
 CONTRACTOR FOR THE SCOPE OF WORK PER THE WPB AMENDMENTS
 TO THE FBC SEC. 105.1.
  
 2. SHOWS THE LENGTH OF ALL CUT SECTIONS OF PIPE PER
 2017 FBC RES. SECS. G2413.4.1, G2413.4.2.
  
 3. SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, ALL
 PIPE SIZES, FOR EACH PIPE SIZE ON ISOMETRIC PER THE WPB
 AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 4. MOST TANKLESS UNIT CALL FOR 10.5" WATER COLUMN AND
 THE SERVICE METER DISCHARGES IS A 2 PSI REQUIRING A
 REGULATOR FOR THIS UNIT AS PER MANUFACTURER'S
 SPECIFICATION. SUBMIT MANUFACTURER'S SPECIFICATIONS FOR
 THE PRESSURE REGULATORS. REGULATORS INSTALLED ON THE
 EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR
 INSTALLATION PER THE 2017 FBC RES. SEC. G2421.1.
 5. SUBMIT CALCULATIONS FOR COMBUSTION AIR FOR STOVE PER
 THE FBC RES. SEC. G2407.1 AND G2439.4
  
 6. SUBMIT MANUFACTURER'S SPECIFICATION
 SHEETS/INSTALLATION MANUAL FOR STOVE AND TANKLESS
 HEATER EQUIPMENT TO VERIFY COMPLIANCE WITH 2017 FBC
 RES. SEC. G2408.1.
  
 7. PLEASE LABEL AND SHOW ALL UNIONS IN FRONT OF
 REGULATOR 1' OF EITHER SIDE PER THE 2017 FBC RES. SEC
 G2421.2 OR 2017 FBC FG SEC 410.2.
  
 8. PLEASE LABEL THE SHUTOFF VALVE ON GAS ISOMERIC PER
 THE 2017 FBC RES. SEC. G2401.1.3.
  
 9. PLEASE SHOW AND LABEL DRIP LEG ON EQUIPMENT
 INSTALLED PER THE 2017 FBC RES. SEC. G2419.
  
 10. IF THIS UNIT REQUIRES CONDENSATE IT MUST BE 1' AWAY
 FROM STRUCTURE PER THE 2017 FBC SEC R318.5.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  