| 2020-09-21 17:59:47 | RESIDENTIAL (R3) ADDITION BUILDING REVIEW COMMENTS |
| | CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. |
| | |
| | NOTE: |
| | BUILDING REVIEW MAY BE APPROVED WITH PROVISO. PROVISO |
| | MEANS CONTRACTOR WILL SUBMIT REQUIRED INFORMATION AFTER |
| | THE PERMIT IS ISSUED BUT BEFORE INSPECTIONS TO AVOID |
| | CONFLICTS/DELAYS. REVISION FEES MAY APPLY. CONTRACTOR |
| | TO ADVICE IF PROVISO OPTION IS PREFERRED AT THIS TIME |
| | OR IF RE-SUBMITTING REQUIRED INFORMATION BEFORE PERMIT |
| | ISSUANCE. |
| | |
| | IMPORTANT: |
| | THE ENERGY CALCULATIONS NEED TO BE SIGNED BY THE OWNER, |
| | ARCHITECT OR LEGALLY DESIGNATED AGENT PRIOR TO RECEIVE |
| | THE PERMIT. SEE ITEM #5(A) BELOW. |
| | |
| | |
| | 1- ALL THE ARCHITECTURAL WALL SECTIONS SHOW R30 BATT |
| | INSULATION IN THE CEILING AREA. ARCHITECTURAL AND |
| | STRUCTURAL PLANS SHOW THAT THE CEILING INSULATION WILL |
| | BE FIT BETWEEN THE 2X6 PURLINS. R30 BATT INSULATION |
| | DOESN'T FIT IN THE SPACE PROVIDED BY THE 2X6 PURLINS. |
| | R30 BAT INSULATION IS 9-1/2" THICK +/-. NEED TO REVISE |
| | AS REQUIRED. |
| | NOTE: COORDINATE WITH THE ENERGY CALCULATIONS TO AVOID |
| | CONFLICTS/DELAYS. |
| | SEC. 107.2.1 CITY AMENDMENTS. |
| | |
| | 2- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| | FAC 61G20-3.001 FOR |
| | (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED |
| | SUBMITTAL. PROVIDE COMPLETE INFORMATION PRIOR TO |
| | INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL PRODUCT |
| | APPROVALS NEED TO BE APPROVED IN WRITING BY DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL): |
| | |
| | A)ROOF TILE AND SPECIFY FASTENING. IF SPECIFYING ROOF |
| | TILE ADHESIVE, THEN PROVIDE PRODUCT APPROVAL. IF |
| | SPECIFYING SCREWS, THEN SPECIFY SCREW SIZE AND NUMBER |
| | OF SCREWS. |
| | |
| | B)ROOF TILE ADHESIVE. SEE ROOF TILE NOA SUBMITTED FOR |
| | LISTED ADHESIVES. AND CLEARLY MARK PADDY SIZE AS |
| | REQUIRED BY CITY POLICY FOR ALL ROOFING PERMITS. |
| | |
| | C)FLAT ROOF AS SHOWN ON PLANS. AND, CLEARLY MARK WHICH |
| | APPROVED ASSEMBLY IS GOING TO BE INSTALLED TO VERIFY |
| | COMPLIANCE WITH THE DESIGN PRESSURES OF SEC. R301.1 |
| | FBC-RESIDENTIAL. |
| | NOTE: IF THE SELECTED ASSEMBLY DOESN'T MEET THE DESIGN |
| | PRESSURES FOR ALL ROOF ZONES, THEN SIGNED AND SEALED |
| | RAS 117 CALCULATIONS ARE REQUIRED. |
| | |
| | D)ENTRY DOOR. |
| | E)LAUNDRY DOOR. |
| | F)SLIDING GLASS DOORS. |
| | G)FIXED WINDOWS. |
| | H)HORIZONTAL SLIDING WINDOWS. |
| | I)CASEMENT WINDOWS. |
| | I)OVERHEAD GARAGE DOOR. |
| | |
| | 3- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS |
| | REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. |
| | |
| | 4-FRAMED GABLE ENDS: |
| | A)NEED TO SPECIFY THE 7/8" MIN. STUCCO THICKNESS AS |
| | REQUIRED BY TABLE R702.1(1) FBC-RESIDENTIAL |
| | |
| | B) NEED TO SPECIFY 2 LAYERS OF WATER RESISTIVE BARRIERS |
| | AS REQUIRED BY SEC. R703.7.3 FBC-RESIDENTIAL ON THE |
| | WOOD FRAMED WALL. |
| | |
| | 5- ENERGY CALCULATIONS: |
| | A)ENERGY CALCULATIONS FORM IS REQUIRED TO BE CERTIFIED |
| | AT THE BOTTOM OF THE FORM BY THE OWNER, THE OWNER'S |
| | ARCHITECT OR OTHER AUTHORIZED AGENT LEGALLY DESIGNED BY |
| | THE OWNER PRIOR TO RECEIVE THE PERMIT AS REQUIRED BY |
| | SEC. R103.1.1.2 FBC-ENERGY CONSERVATION, 6TH EDITION |
| | (2017). |
| | |
| | B)REVISE THE DESIGN LOCATION SPECIFIED ON TOP OF FORM |
| | SUBMITTED. THIS IS CITY OF WEST PALM BEACH NOT MIAMI. |
| | SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION. |
| | |
| | C)PROVIDE COMPLETE AND CORRECT INFORMATION ON TOP OF |
| | FORM. THE CORRECT ZIP CODE FOR THIS ADDRESS IS 33405 |
| | NOT 33145. ALSO, REVISE THE DESIGN LOCATION. THIS IS |
| | CITY OF WEST PALM BEACH NOT MIAMI. ALSO, PROVIDE THE |
| | BUILDER NAME, PERMIT OFFICE. SEC. R101.5.1.1.2 |
| | FBC-ENERGY CONSERVATION. |
| | |
| | D)ITEM #8A ON PAGE 1 OF 5 SPECIFIES R3 SLAB ON GRADE |
| | EDGE INSULATION. PLANS DON'T SPECIFY ANY SLAB EDGE |
| | INSULATION. REVISE AS REQUIRED. SEC. R101.5.1.1.2 |
| | FBC-ENERGY CONSERVATION. |
| | |
| | E)INFORMATION AND INSULATION SPECIFIED ON ITEMS #9A, |
| | #9B AND #9C DOESN'T MATCH PLANS. REVISE AS REQUIRED. |
| | THERE IS NOT CONCRETE BLOCK EXTERIOR INSULATION AND |
| | THERE IS NOT FACE BRICK. SEC. R101.5.1.1.2 FBC-ENERGY |
| | CONSERVATION. |
| | |
| | F)CEILING INFORMATION ON ITEM #10 NEEDS TO BE |
| | COORDINATED WITH THE REVISED ARCHITECTURAL PLANS. SEE |
| | ITEM #1 ABOVE. COORDINATE WITH ARCHITECT TO AVOID |
| | CONFLICTS/DELAYS. SEC. 107.2.1 CITY AMENDMENTS. |
| | |
| | G)REVISE CLIMATE INFORMATION ON PAGE 2 OF 5. DESIGN |
| | LOCATION IS WEST PALM BEACH NOT MIAMI. SEC. |
| | R101.5.1.1.2 FBC-ENERGY CONSERVATION. |
| | |
| | H)REVISE ROOF TYPE ON PAGE 2 OF 5. PLANS DON'T SPECIFY |
| | SHINGLES. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION. |
| | |
| | I)REVISE DOORS INFORMATION ON PAGE 3 OF 5. PLANS DON'T |
| | SPECIFY WOOD DOORS. SEC. R101.5.1.1.2 FBC-ENERGY |
| | CONSERVATION. |
| | |
| | J)REVISE THE WINDOWS OVERHANG DEPTH AND SEPARATION TO |
| | MATCH PLANS. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION. |
| | |
| | WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE |
| | ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF |
| | THE REVISION MADE, IDENTIFYING THE SHEET OR |
| | SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL |
| | HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR |
| | ANTICIPATED COOPERATION. |
| | |
| | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY |
| | QUESTIONS REGARDING THESE COMMENTS, |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | BUILDING DIVISION |
| | (561)805-6712 |
| | [email protected] |
| | |