Plan Review Notes
Plan Review Notes For Permit 20080481
Permit Number 20080481
Review Stop B
Sequence Number 1
Notes
Date Text
2020-09-21 17:59:47RESIDENTIAL (R3) ADDITION BUILDING REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 NOTE:
 BUILDING REVIEW MAY BE APPROVED WITH PROVISO. PROVISO
 MEANS CONTRACTOR WILL SUBMIT REQUIRED INFORMATION AFTER
 THE PERMIT IS ISSUED BUT BEFORE INSPECTIONS TO AVOID
 CONFLICTS/DELAYS. REVISION FEES MAY APPLY. CONTRACTOR
 TO ADVICE IF PROVISO OPTION IS PREFERRED AT THIS TIME
 OR IF RE-SUBMITTING REQUIRED INFORMATION BEFORE PERMIT
 ISSUANCE.
  
 IMPORTANT:
 THE ENERGY CALCULATIONS NEED TO BE SIGNED BY THE OWNER,
 ARCHITECT OR LEGALLY DESIGNATED AGENT PRIOR TO RECEIVE
 THE PERMIT. SEE ITEM #5(A) BELOW.
  
  
 1- ALL THE ARCHITECTURAL WALL SECTIONS SHOW R30 BATT
 INSULATION IN THE CEILING AREA. ARCHITECTURAL AND
 STRUCTURAL PLANS SHOW THAT THE CEILING INSULATION WILL
 BE FIT BETWEEN THE 2X6 PURLINS. R30 BATT INSULATION
 DOESN'T FIT IN THE SPACE PROVIDED BY THE 2X6 PURLINS.
 R30 BAT INSULATION IS 9-1/2" THICK +/-. NEED TO REVISE
 AS REQUIRED.
 NOTE: COORDINATE WITH THE ENERGY CALCULATIONS TO AVOID
 CONFLICTS/DELAYS.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 2- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.001 FOR
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL. PROVIDE COMPLETE INFORMATION PRIOR TO
 INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL PRODUCT
 APPROVALS NEED TO BE APPROVED IN WRITING BY DESIGNER OF
 RECORD PRIOR TO SUBMITTAL):
  
 A)ROOF TILE AND SPECIFY FASTENING. IF SPECIFYING ROOF
 TILE ADHESIVE, THEN PROVIDE PRODUCT APPROVAL. IF
 SPECIFYING SCREWS, THEN SPECIFY SCREW SIZE AND NUMBER
 OF SCREWS.
  
 B)ROOF TILE ADHESIVE. SEE ROOF TILE NOA SUBMITTED FOR
 LISTED ADHESIVES. AND CLEARLY MARK PADDY SIZE AS
 REQUIRED BY CITY POLICY FOR ALL ROOFING PERMITS.
  
 C)FLAT ROOF AS SHOWN ON PLANS. AND, CLEARLY MARK WHICH
 APPROVED ASSEMBLY IS GOING TO BE INSTALLED TO VERIFY
 COMPLIANCE WITH THE DESIGN PRESSURES OF SEC. R301.1
 FBC-RESIDENTIAL.
 NOTE: IF THE SELECTED ASSEMBLY DOESN'T MEET THE DESIGN
 PRESSURES FOR ALL ROOF ZONES, THEN SIGNED AND SEALED
 RAS 117 CALCULATIONS ARE REQUIRED.
  
 D)ENTRY DOOR.
 E)LAUNDRY DOOR.
 F)SLIDING GLASS DOORS.
 G)FIXED WINDOWS.
 H)HORIZONTAL SLIDING WINDOWS.
 I)CASEMENT WINDOWS.
 I)OVERHEAD GARAGE DOOR.
  
 3- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 4-FRAMED GABLE ENDS:
 A)NEED TO SPECIFY THE 7/8" MIN. STUCCO THICKNESS AS
 REQUIRED BY TABLE R702.1(1) FBC-RESIDENTIAL
  
 B) NEED TO SPECIFY 2 LAYERS OF WATER RESISTIVE BARRIERS
 AS REQUIRED BY SEC. R703.7.3 FBC-RESIDENTIAL ON THE
 WOOD FRAMED WALL.
  
 5- ENERGY CALCULATIONS:
 A)ENERGY CALCULATIONS FORM IS REQUIRED TO BE CERTIFIED
 AT THE BOTTOM OF THE FORM BY THE OWNER, THE OWNER'S
 ARCHITECT OR OTHER AUTHORIZED AGENT LEGALLY DESIGNED BY
 THE OWNER PRIOR TO RECEIVE THE PERMIT AS REQUIRED BY
 SEC. R103.1.1.2 FBC-ENERGY CONSERVATION, 6TH EDITION
 (2017).
  
 B)REVISE THE DESIGN LOCATION SPECIFIED ON TOP OF FORM
 SUBMITTED. THIS IS CITY OF WEST PALM BEACH NOT MIAMI.
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 C)PROVIDE COMPLETE AND CORRECT INFORMATION ON TOP OF
 FORM. THE CORRECT ZIP CODE FOR THIS ADDRESS IS 33405
 NOT 33145. ALSO, REVISE THE DESIGN LOCATION. THIS IS
 CITY OF WEST PALM BEACH NOT MIAMI. ALSO, PROVIDE THE
 BUILDER NAME, PERMIT OFFICE. SEC. R101.5.1.1.2
 FBC-ENERGY CONSERVATION.
  
 D)ITEM #8A ON PAGE 1 OF 5 SPECIFIES R3 SLAB ON GRADE
 EDGE INSULATION. PLANS DON'T SPECIFY ANY SLAB EDGE
 INSULATION. REVISE AS REQUIRED. SEC. R101.5.1.1.2
 FBC-ENERGY CONSERVATION.
  
 E)INFORMATION AND INSULATION SPECIFIED ON ITEMS #9A,
 #9B AND #9C DOESN'T MATCH PLANS. REVISE AS REQUIRED.
 THERE IS NOT CONCRETE BLOCK EXTERIOR INSULATION AND
 THERE IS NOT FACE BRICK. SEC. R101.5.1.1.2 FBC-ENERGY
 CONSERVATION.
  
 F)CEILING INFORMATION ON ITEM #10 NEEDS TO BE
 COORDINATED WITH THE REVISED ARCHITECTURAL PLANS. SEE
 ITEM #1 ABOVE. COORDINATE WITH ARCHITECT TO AVOID
 CONFLICTS/DELAYS. SEC. 107.2.1 CITY AMENDMENTS.
  
 G)REVISE CLIMATE INFORMATION ON PAGE 2 OF 5. DESIGN
 LOCATION IS WEST PALM BEACH NOT MIAMI. SEC.
 R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 H)REVISE ROOF TYPE ON PAGE 2 OF 5. PLANS DON'T SPECIFY
 SHINGLES. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 I)REVISE DOORS INFORMATION ON PAGE 3 OF 5. PLANS DON'T
 SPECIFY WOOD DOORS. SEC. R101.5.1.1.2 FBC-ENERGY
 CONSERVATION.
  
 J)REVISE THE WINDOWS OVERHANG DEPTH AND SEPARATION TO
 MATCH PLANS. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION