| 2020-10-02 12:11:36 | PLAN |
| | REVIEW COMMENTS |
| | |
| | 1ST REVIEW: FBC SIXTH EDITION (2017) |
| | ROBERT MCDOUGAL, CBO |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561) 805-6714 |
| | [email protected] |
| | |
| | DENIED BY BUILDING |
| | PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| | |
| | 1) CIRCLE OR HI-LIGHT THE APPROPIATE ITEMS THAT APPLY |
| | TO THIS PROJECT (SUCH AS SIZE, GLASS TYPE, DESIGN |
| | PRESSURE) ON THE PRODUCT APPROVALS. FBC 107 |
| | |
| | 2) THE CONTRACT THAT WAS SUBMITTED IS FOR ANOTHER |
| | PROJECT. FBC 107.2.1 |
| | |
| | 3) INDICATED ON THE FLOOR PLAN THE LOCATION OF THE |
| | BEDROOMS AND SHOW THE EMERGENCY ESCAPE AND RESCUE |
| | OPENINGS WILL COMPLY WITH FBC EXISTING BUILDING SECTION |
| | 702.5 EMERGENCY ESCAPE AND RESCUE OPENINGS. WHERE |
| | WINDOWS ARE REQUIRED TO PROVIDE EMERGENCY ESCAPE AND |
| | RESCUE OPENINGS IN GROUP R-2 AND R-3 OCCUPANCIES AND |
| | ONE- AND TWO-FAMILY DWELLINGS AND TOWNHOUSES REGULATED |
| | BY THE FLORIDA BUILDING CODE, RESIDENTIAL, REPLACEMENT |
| | WINDOWS SHALL BE EXEMPT FROM THE REQUIREMENTS OF |
| | SECTIONS 1030.2, 1030.3 AND 1030.5 OF THE FLORIDA |
| | BUILDING CODE, BUILDING AND SECTIONS R310.21 AND |
| | R310.2.3 OF THE FLORIDA BUILDING CODE, RESIDENTIAL |
| | ACCORDINGLY, PROVIDED THE REPLACEMENT WINDOW IS THE |
| | MANUFACTURER'S LARGEST STANDARD SIZE WINDOW THAT WILL |
| | FIT WITHIN THE EXISTING FRAME OR EXISTING ROUGH |
| | OPENING. THE REPLACEMENT WINDOW SHALL BE PERMITTED TO |
| | BE OF THE SAME OPERATING STYLE AS THE EXISTING WINDOW |
| | OR A STYLE THAT PROVIDES FOR AN EQUAL OR GREATER WINDOW |
| | OPENING AREA THAN THE EXISTING WINDOW. |
| | |