| 2020-09-11 12:38:01 | PLAN | | | REVIEW COMMENTS | | | | | | 2ND REVIEW: FBC SIXTH EDITION (2017) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THE AIR BORNE AND STRUCTURE BORNE TEST REPORTS THAT | | | WERE SUBMITTED DO NOT REFLECT THE SITE CONDITIONS OF | | | THE PROJECT. SUBMIT THE TEST REPORTS FOR A 6" CONCRETE | | | FLOOR SLAB ASSEMBLY WITH NO CEILING OR INSULATION | | | BELOW. THE REPORTS THAT WERE SUBMITTED HAVE A WOOD | | | FRAME ASSEMBLY WITH 8" OF INSULATION. | | | FBC 1207.2 AIR-BORNE SOUND. ASTM E 90-04, FBC 1207.3 | | | STRUCTURE-BORNE SOUND. ASTM E 492-09 | | | | | | |
|