2020-09-17 16:47:561ST REVIEW FBC-2017 RES.
 PERMIT- 20080457
 9/10/2020
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) GAS RISER:
 A) TOTAL DEVELOPED LENGTH OF THE SYSTEM NOT SHOWN-
 SECTION G2413.4.1 FBC RES.
 B) TOTAL BRANCH LENGTHS TO GENERATOR, EXISTING INTERIOR
 APPLIANCES, AND EXTERIOR POOL HEATER NOT SHOWN- SECTION
 G2413.4.2
 C) TYPES AND SIZES OF BRANCH PIPING NOT SHOWN- SECTION
 G2413.3.
 D) PIPE SIZING TABLES NOT PROVIDED- TABLES G2413.4(1)-
 G2413.4(8).
 E) THE NOTE SHOWING NEW 1.25 PE GAS LINE TO GENERATOR
 NOTE CONFLICTS WITH THE DRAWING THAT SHOWS METALLIC
 PIPING RUN SHOWN TO GENERATOR- SECTION 107.2.1 WPB
 F) ESTIMATED LOAD A TO B INDICATES 1.25 IN PIPE
 REQUIRED, BUT 1 IN. IS SHOWN ON DRAWING- 107.2.1.
 G) ESTIMATED LOAD B TO C NOT SHOWN AND ESTIMATED LOAD C
 TO D APPEARS TO BE MISLABELED- THERE IS NO D ON
 DRAWING- 107.2.1.
 H) INDICATE HOW THE PE PIPING RISER WILL CONNECT TO THE
 SCHEDULE 40 METALLIC PIPE PER SECTIONS G2415.17.1 &
 G2415.17.2 FBC RES. PLEASE NOTE THAT SPECS FOR
 ANODELESS RISERS AND PE/METALLIC PIPE CONNECTORS SHALL
 BE LISTED AND LABELED AND SHALL BE ONSITE ART TIME OF
 INSPECTION
 I) PROVIDE THE MAKE AND MODEL NUMBER OF THE REGULATOR,
 AND SHOW THE REQUIRED PIPE UNION LOCATIONS AT EACH SIDE
 OF THE REGULATOR SECTION G2421.2.
  
 2) REVISE THE MARKED-UP SURVEY TO SHOW THE UG PE RUN-
 SECTION 107.2.1 WPB. PLEASE NOTE THE GENERATOR SHALL BE
 INSTALLED A MINIMUM OF 5 FT. FROM COMBUSTIBLE WALLS.
 THE 18 IN. CLEARANCE DISTANCE SHALL BE PERMITTED IF THE
 HOUSE WALL HAS A 1-HR. FIRE RESISTANCE RATING, OR THE
 GENERATOR HAS A WEATHERPROOF ENCLOSURE CONSTRUCTED OF
 NON-COMBUSTIBLE MATERIALS AND IT HAS BEEN DEMONSTRATED
 THAT A FIRE WITHIN THE ENCLOSURE WILL NOT IGNITE
 COMBUSTIBLE MATERIALS OUTSIDE OF THE ENCLOSURE- SECTION
 4.1.4 NFPA 37. THE SUBMITTED GENERIC GUIDELINES
 INDICATE LOCAL CODES TAKE PRECEDENCE.
  
 3) THE SIGNATURE OF FL. LICENSED GAS CONTRACTOR AND
 LICENSE NUMBER SHALL BE ON THE GAS RISER DRAWING PER
 SECTION 107.2.1 WPB, AND FL. STATURES 471.003 &
 471.025.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  