Plan Review Notes
Plan Review Notes For Permit 20080457
Permit Number 20080457
Review Stop G
Sequence Number 1
Notes
Date Text
2020-09-10 10:45:491ST REVIEW FBC-2017 RES.
 PERMIT- 20080457
 9/10/2020
  
 CODES IN EFFECT:
  
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE A GAS ISOMETRIC DRAWING PER SECTION
 107.3.5.3 WPB, AND SECTIONS G2413.4.1 & G2413.4.2 FBC
 RES. BECAUSE A 310,000 BTUH GENERATOR IS BEING ADDED TO
 AN EXISTING GAS PIPING SYSTEM, IN ORDER TO ENSURE A
 SAFE OPERATING SYSTEM, THE ISOMETRIC SHALL BE A
 COMPLETE REPRESENTATION OF THE NEW AND EXISTING GAS
 PIPING SYSTEM INCLUDING ALL PIPING RUNS TO EXISTING GAS
 APPLIANCES INSTALLED UNDER PERMIT #05061739- POOL
 HEATER, BBQ, COOKTOP, WATER HEATER, DRYER; AND ANY
 OTHER APPLIANCES CURRENTLY INSTALLED AT THE RESIDENCE-
 SECTIONS G2412.3 & G2412.4 FBC RES. THE DRAWING SHALL
 SHOW THE TYPES AND SIZES OF PIPING, LONGEST RUN LENGTH
 FROM THE METER TO THE MOST REMOTE OUTLET, BRANCH LENGTH
 SIZES, DELIVERY PRESSURE AT THE METER AND LOCATIONS OF
 REGULATORS AND STEP DOWN PRESSURES, BTUH LOAD OF EACH
 APPLIANCE AND THE TOTAL LOAD OF THE SYSTEM- SECTIONS
 G2413.2, G2413.3, G2413.4, G2413.4.1, G2413.4.2,
 G2414.1, G2420.1, G2421.1 & G2421.2 FBC RES.
  
 2) PLEASE SUBMIT A COMPLETE SPECIFICATION SHEET FOR THE
 FLEX CONNECTOR THAT INDICATES MANUFACTURER AND MODEL,
 LISTING STANDARDS, AND INSTALLATION GUIDELINES- SECTION
 G2415.1 FBC RES.
  
 3) PLEASE MARK UP THE B42 SERIES REGULATOR SPECS TO
 INDICATE THE MODEL NUMBER, INLET PRESSURE, ORIFICE AND
 SPRING SIZE OF THE SELECTED REGULATOR- SECTION G2421.1
 & G2421.2 FBC RES.
  
 4) SUBMIT INSTALLATION GUIDELINES FROM GENERAC TO
 VERIFY THE ALLOWABLE CLEARANCES FOR THE GENERATOR TO
 THE BUILDING, OPERABLE OPENINGS INTO THE BUILDING, AND
 PROPERTY LINES- SECTION 107.2.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  