| 2020-09-10 10:45:49 | 1ST REVIEW FBC-2017 RES. |
| | PERMIT- 20080457 |
| | 9/10/2020 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| | EDITION 2017 |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PROVIDE A GAS ISOMETRIC DRAWING PER SECTION |
| | 107.3.5.3 WPB, AND SECTIONS G2413.4.1 & G2413.4.2 FBC |
| | RES. BECAUSE A 310,000 BTUH GENERATOR IS BEING ADDED TO |
| | AN EXISTING GAS PIPING SYSTEM, IN ORDER TO ENSURE A |
| | SAFE OPERATING SYSTEM, THE ISOMETRIC SHALL BE A |
| | COMPLETE REPRESENTATION OF THE NEW AND EXISTING GAS |
| | PIPING SYSTEM INCLUDING ALL PIPING RUNS TO EXISTING GAS |
| | APPLIANCES INSTALLED UNDER PERMIT #05061739- POOL |
| | HEATER, BBQ, COOKTOP, WATER HEATER, DRYER; AND ANY |
| | OTHER APPLIANCES CURRENTLY INSTALLED AT THE RESIDENCE- |
| | SECTIONS G2412.3 & G2412.4 FBC RES. THE DRAWING SHALL |
| | SHOW THE TYPES AND SIZES OF PIPING, LONGEST RUN LENGTH |
| | FROM THE METER TO THE MOST REMOTE OUTLET, BRANCH LENGTH |
| | SIZES, DELIVERY PRESSURE AT THE METER AND LOCATIONS OF |
| | REGULATORS AND STEP DOWN PRESSURES, BTUH LOAD OF EACH |
| | APPLIANCE AND THE TOTAL LOAD OF THE SYSTEM- SECTIONS |
| | G2413.2, G2413.3, G2413.4, G2413.4.1, G2413.4.2, |
| | G2414.1, G2420.1, G2421.1 & G2421.2 FBC RES. |
| | |
| | 2) PLEASE SUBMIT A COMPLETE SPECIFICATION SHEET FOR THE |
| | FLEX CONNECTOR THAT INDICATES MANUFACTURER AND MODEL, |
| | LISTING STANDARDS, AND INSTALLATION GUIDELINES- SECTION |
| | G2415.1 FBC RES. |
| | |
| | 3) PLEASE MARK UP THE B42 SERIES REGULATOR SPECS TO |
| | INDICATE THE MODEL NUMBER, INLET PRESSURE, ORIFICE AND |
| | SPRING SIZE OF THE SELECTED REGULATOR- SECTION G2421.1 |
| | & G2421.2 FBC RES. |
| | |
| | 4) SUBMIT INSTALLATION GUIDELINES FROM GENERAC TO |
| | VERIFY THE ALLOWABLE CLEARANCES FOR THE GENERATOR TO |
| | THE BUILDING, OPERABLE OPENINGS INTO THE BUILDING, AND |
| | PROPERTY LINES- SECTION 107.2.1 WPB. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL/PLUMBING PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | [email protected] |
| | |