| Plan Review Notes For Permit 20080399 |
| Permit Number |
20080399 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2020-09-11 11:01:27 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | FLORIDA BUILDING CODE 2017 6TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | | NFPA 70 2014 EDITION | | | | | | JAKE LEAHY BN, BU, PX | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | NO ELECTRIC SHOWN, PLEASE SUBMIT A PLAN SHOWING ANY | | | ELECTRICAL WORK IF NONE PLEASE NOTE ON PLANS. |
|