2020-10-01 14:07:57ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 A/C AT COTTAGE ARE FED FROM A DIFFERENT SOURCE PER
 225.31 YOU WILL NEED TO SET A DISCONNECT NEXT TO THE
 PANEL ON THE OUTSIDE OF THE COOTAGE AND LABEL IT A 1 OF
 2 AND 2 OF 2 FOR THE DISCONNECTING MEANS TO THE
 COTTAGE.